Issue 07/04
2.3

Mechanical installation

WARNING
To ensure the safe operation of the equipment, it must be installed and
commissioned by qualified personnel in full compliance with the warnings laid
down in these operating instructions.
Take particular note of the general and regional installation and safety
regulations regarding work on dangerous voltage installations (e.g. EN
50178), as well as the relevant regulations regarding the correct use of tools
and personal protective gear.
The mains input, DC and motor terminals, can carry dangerous voltages even
if the inverter is inoperative; wait 5 minutes to allow the unit to discharge after
switching off before carrying out any installation work.
The inverters can be mounted adjacent to each other. If they are mounted on
top of each other, however, a clearance of 100 mm has to be observed.
Frame Size A
55 mm
2.2"
160 mm
6.30"
Ø 4.5 mm
0.17"
Fig. 2-4
Drill pattern for MICROMASTER 420
Table 2-1
Dimensions and Torques of MICROMASTER 420
Frame-Size
Overall Dimensions
mm
Width x
A
Height x
inch
Depth
Width x
mm
B
Height x
inch
Depth
Width x
mm
C
Height x
inch
Depth
MICROMASTER 420
Operating Instructions
6SE6400-5AA00-0BP0
4
Frame Size B
Ø 4.8 mm
0.19"
138 mm
5.43"
Fixing Method
73 x 173 x 149
2 x M4 Bolts
2 x M4 Nuts
2 x M4 Washers for mounting on
2.87 x 6.81 x 5.87
149 x 202 x 172
4 x M4 Bolts
4 x M4 Nuts
5.87 x 7.95 x 6.77
4 x M4 Washers
185 x 245 x 195
4 x M5 Bolts
4 x M5 Nuts
7.28 x 9.65 x 7.68
4 x M5 Washers
Frame Size C
174 mm
6.85"
standard rail
2 Installation
Ø 5.5 mm
0.22"
204 mm
8.03"
174 mm
6.85"
Tightening Torque
2.5 Nm
with washers fitted
2.5 Nm
with washers fitted
2.5 Nm
with washers fitted
25