INSTALLING A REMOTE EMERGENCY POWER-OFF CONTROL
5-2
EATON Powerware
NOTE REPO switch rating is 24 Vdc, 1A minimum if supplied by the customer. The REPO switch must be a
latching-type switch with a dedicated circuit.
5.
If you are installing multiple REPO stations, wire additional stations in parallel
with the first REPO.
6.
If required, install ½" conduit and wiring from the REPO station to trip circuitry of
upstream protective devices. A normally open contact is provided, as shown in
Figure 5-2. REPO switch wiring must be according to UL Class I requirements.
7.
Secure the UPS by reversing all steps taken to prepare it for REPO installation.
®
9315 UPS (500–750 kVA) Installation and Operation Manual
9
REPO
CUSTTB
Switch
10
Twisted
Wires (2)

Figure 5-2. REPO Wiring

S
164201691 Rev 1 www.powerware.com