Eaton 93PM-L Series Installation And Operation Manual
Eaton 93PM-L Series Installation And Operation Manual

Eaton 93PM-L Series Installation And Operation Manual

20 – 60 kw (208v)
Table of Contents

Advertisement

Eaton® 93PM-L UPS
20 – 60 kW (208V) UPS
Installation and Operation Manual
p/n: P-164000711
Revision 03

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 93PM-L Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton 93PM-L Series

  • Page 1 Eaton® 93PM-L UPS 20 – 60 kW (208V) UPS Installation and Operation Manual p/n: P-164000711 Revision 03...
  • Page 2 NEC are registered trademarks of National Fire Protection Association, Inc. ERIFLEX and FLEXIBAR are registered trademark of Erico International Corporation. All other trademarks are property of their respective companies. ©Copyright 2017-2019 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 3 5.10 Third Party Intellectual Property Rights. The Firmware may contain components transfer the Firmware directly to a third party only in connection with the sale of the Eaton (including open source software components) that are owned by third parties (“Third Party product in which it is installed.
  • Page 5 4 4 U U P P S S S S y y s s t t e e m m I I n n s s t t a a l l l l a a t t i i o o n n ....................................................5 5 5 5 4.1 Preliminary Installation Information....................... 55 4.2 Unloading the UPS Cabinet from the Pallet..................... 55 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 6 6.2.3 Using the LCD Touch Screen....................... 113 6.2.4 Using the Menu..........................114 6.2.5 Mimic Screen ..........................115 6.2.6 Display Menu Operation........................116 6.2.7 Sign In............................121 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 7 7 7 C C o o m m m m u u n n i i c c a a t t i i o o n n ........................................................1 1 4 4 1 1 7.1 Minislot Cards............................141 7.2 Building Alarm Monitoring ........................141 7.3 General Purpose Relay Contact ......................... 142 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 8 1 1 0 0 W W a a r r r r a a n n t t y y ........................................................... . 1 1 5 5 1 1 viii Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 9 Eaton 93PM-L UPS (60 kW, Four-Wire) with Top Entry Wiring Sidecar ............2 Figure 3. Eaton 93PM-L UPS (60 kW, Four-Wire) with Bypass Sidecar (2, 3 or 4 Breaker SIAC-B) ......... 3 Figure 4. UPS Cabinet Dimensions (Front and Right Side Views)................. 18 Figure 5.
  • Page 10: Table Of Contents

    Typical EAA Control Screen ......................126 Figure 77. REPO Operation ........................133 Figure 78. Optional Minislot Cards ....................... 141 Figure 79. Air Filter Location ........................147 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 11 Display Menu Operation ....................... 116 Table 32. Controls Menu Operation ......................123 Table 33. Typical System Status Messages....................124 Table 34. IRC-MS Default Triggers ....................... 141 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 12 List of Tables Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 13 The Eaton 93PM-L UPS is available with up to three Uninterruptible Power Modules (UPMs) integrated in one cabinet. Each UPM is rated for a maximum of 20 kW. The system maximum rating is 60 kW. To deliver greater reliability, a UPS with two or more UPMs can provide N+1 redundancy up to a maximum of 40 kW.
  • Page 14 Figure 1. Eaton 93PM-L UPS (60 kW, Four-Wire) Figure 2. Eaton 93PM-L UPS (60 kW, Four-Wire) with Top Entry Wiring Sidecar UPS with Left-Mounted UPS with Right-Mounted Top Entry Sidecar Top Entry Sidecar Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 15 Introduction Figure 3. Eaton 93PM-L UPS (60 kW, Four-Wire) with Bypass Sidecar (2, 3 or 4 Breaker SIAC-B) UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar 1 1 . . 1 1 . . 2 2 C C o o n n t t r r o o l l P P a a n n e e l l...
  • Page 16 1 1 . . 1 1 . . 5 5 I I n n t t e e r r n n a a l l R R e e d d u u n n d d a a n n c c y y To deliver greater reliability, the Eaton 93PM-L UPS can be configured for internal redundancy. When configured, the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM.
  • Page 17 UPS from virtually any location within the facility, up to 300 feet from the UPS. Refer to the Eaton Remote Monitoring Device (RMD) Installation and Operation Manual, listed in paragraph 1.8 For More...
  • Page 18 Type 2 installed on the load side is recommended. The SPD must meet the Maximum Continuous Operating Voltage (MCOV) for a 208V Delta Style SPD. Eaton offers a variety of SPD solutions including the Eaton SPD Series with various kA ratings options.
  • Page 19 U U s s i i n n g g T T h h i i s s M M a a n n u u a a l l This manual describes how to install and operate the Eaton 93PM-L UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation.
  • Page 20 SIAC-B, 120 kW Top Entry Wiring Sidecar, and 120 kW SIAC-B) Installation and Operation Manual Phillips and Pozidriv are registered trademarks of Phillips Screw Company. ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be for the following additional information: Eaton, Powerware, and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates.
  • Page 21 1 1 . . 1 1 0 0 E E q q u u i i p p m m e e n n t t R R e e g g i i s s t t r r a a t t i i o o n n Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory. Model Number: Serial Number: Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 22 Introduction Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 23 • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 24 Ne pas fumer près des accumulateurs. Ne pas produire de flamme ou d’étincelle dans la zone de l’accumulateur. Dissiper l'électricité statique de votre corps en touchant une surface reliée à la terre avant de toucher les accumulateurs. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 25 There shall be at least a 1.8°F (1.0°C) difference between the dry bulb temperature and the wet bulb temperature, at all times, to maintain a non-condensing environment. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 26 Sizing the site cooling infrastructure to be capable of cooling the maximum kW frame size will allow a full power rating upgrade without having to modify the infrastructure. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 27 (2+1), 3 Battery Strings 666 (1465) 635 (1398) 4 at 159 (350) 3 UPMs Installed 4 Battery Strings 755 (1660) 724 (1593) 4 at 181 (398) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 28 (2+1), 3 Battery 3 UPMs Installed 813 (1787) 782 (1720) 6 at 130 (287) Strings 4 Battery Strings 901 (1982) 870 (1915) 6 at 145 (319) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 29 Allow clearance in front of and on top or in back of the cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in the following table. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 30 None Required From Left Side of Cabinet Figure 4. UPS Cabinet Dimensions (Front and Right Side Views) Front View Side View Dimensions are in millimeters [inches] Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 31 [10.6] [21.3] Front [38.4] BOTTOM ENTRY CONDUIT LANDING BOTTOM VIEW [14.6] FOR AC INPUT, AC OUTPUT AND DC [12.0] [3.7] [14.6] Dimensions are in millimeters [inches] Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 32 [1.5] 382.5 [15.1] Dimensions are in millimeters [inches] NOTE The UPS Front Floor Mounting Bracket’s mounting dimensions are identical to the Rear Floor Mounting Bracket dimensions. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 33 (Dimensions Mirrored for Sidecar Opposite Side) UPS with Bypass Sidecar (SIAC-B) (Top Exhaust Option Shown) (Dimensions Mirrored for Sidecar Opposite Side) Dimensions are in millimeters [inches] Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 34 UPS with Left-Mounted Top Entry Sidecar UPS with Right-Mounted Top Entry Sidecar 763 [30.0] 763 [30.0] 560 [22.0] 560 [22.0] 1880 [74] Dimensions are in millimeters [inches] Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 35 Bottom View UPS with Right-Mounted Top Entry Sidecar UPS with Left-Mounted Top Entry Sidecar (Top Exhaust Option Shown) (Top Exhaust Option Shown) Dimensions are in millimeters [inches] Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 36 UPS with Leftt-Mounted Bypass Sidecar (SIAC-B) UPS with Right-Mounted Bypass Sidecar (SIAC-B) 875 [34.45] 875 [34.45] 560 [22.0] 560 [22.0] 1880 [74] Dimensions are in millimeters [inches] Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 37 [42.0] Bottom View UPS with Left-Mounted Bypass Sidecar UPS with Right-Mounted Bypass Sidecar (Top Exhaust Option Shown) (Top Exhaust Option Shown) Dimensions are in millimeters [inches] Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 38 3 UPMs (2+1), 3 Battery Strings 1076 [42.4] 552 [21.7] 280 [11] 635 (1398) Installed 4 Battery Strings 1105 [43.5] 551 [21.7] 280 [11] 724 (1593) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 39 Figure 13. UPS with Left or Right-Mounted Top Entry Wiring Sidecar Center of Gravity FRONT VIEW SIDE VIEW SIDECAR CAN BE ON LEFT OR RIGHT SIDE "B" "A" "C" Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 40 (2+1), 3 Battery 3 UPMs 1050 [41.3] 551 [21.7] 322 [12.7] 714 (1570) Strings Installed 4 Battery Strings 1080 [42.5] 550 [21.7] 317 [12.5] 802 (1765) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 41 Figure 14. UPS with Left or Right-Mounted SIAC-B Center of Gravity FRONT VIEW SIDE VIEW SIDECAR CAN BE ON LEFT OR RIGHT SIDE "B" "A" "C" Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 42 (2+1), 3 Battery 3 UPMs 1039 [40.9] 560 [22.0] 361 [14.2] 782 (1720) Strings Installed 4 Battery Strings 1068 [42.0] 558 [22.0] 353 [13.9] 870 (1915) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 43 (2+1), 3 Battery 3 UPMs 1039 [40.9] 558 [22.0] 371 [14.6] 801 (1762) Strings Installed 4 Battery Strings 1066 [42.0] 556 [21.9] 362 [14.3] 890 (1957) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 44 (2+1), 3 Battery 3 UPMs 1037 [40.8] 553 [21.8] 379 [14.9] 817 (1797) Strings Installed 4 Battery Strings 1065 [41.9] 552 [21.7] 370 [14.6] 905 (1992) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 45 Refer to national and local electrical codes for acceptable external wiring practices. • To allow for future power upgrades, Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size instead of the derated kW ordered.
  • Page 46 If the maintenance bypass solution being installed does not provide such functionality, DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass. • The Eaton 93PM-L UPS provides backfeed detection and protection through a shunt trip mechanism of the bypass input breaker. IMPORTANT If an Eaton 93PM-L UPS is ordered with: –...
  • Page 47 For external wiring recommendations, including the minimum AWG size of external wiring, see Table 9 through Table 12. Wire sizes listed are for copper wiring only. For external wiring, use only 75°C copper wire. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 48 (each) DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW) For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate DC Input from External Battery (Standalone...
  • Page 49 Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery Cabinet (IBC). Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed.
  • Page 50 Number DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW) For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate Total Amps...
  • Page 51 Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery Cabinet (IBC). Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed.
  • Page 52 (each) DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW) For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate DC Input from External Battery (Standalone...
  • Page 53 Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery Cabinet (IBC). Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed.
  • Page 54 Number DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW) For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate Total Amps...
  • Page 55 Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery Cabinet (IBC). Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed.
  • Page 56 Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load Conical Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load Washer NOTE For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton service representative (see paragraph 1.9 Getting Help).
  • Page 57 500 MCM Manual Hydraulic Crimp Tool 14 Ton Die Set NOTE For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton service representative (see paragraph 1.9 Getting Help). Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See...
  • Page 58 (A, B, C, Neutral, Ground 220 Vac 93PM-L 60-2 40 kW 93PM-L 60-3 (N+1) AC Output 208 or 220 (A, B, C, Neutral, Ground) Battery (Positive, Negative, Ground) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 59 If an output lockable disconnect is required, it is to be supplied by the customer. Table 17 lists the recommended rating for input and bypass circuit breakers. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 60 IMPORTANT If an output breaker is not provided, the wire between the output and the load must be sized the same as the bypass input wire. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 61 30 kW Eaton 93PM-L 60-3 (N+1) Eaton 93PM-L 60-2 40 kW Eaton 93PM-L 60-3 (N+1) Eaton 93PM-L 60-3 50 kW 125A 60 kW 150A Eaton 93PM-L 60-3 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 62 Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac or 28 Vdc. • Recommended alarm relay wiring size is 18 AWG. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 63 Carefully inspect the outer packaging for evidence of damage during transit. CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE...
  • Page 64 Figure 18. UPS Cabinet with Left or Right-Mounted Top Entry Wiring Sidecar as Shipped on Pallet UPS with Left-Mounted UPS with Right-Mounted Top Entry Sidecar Top Entry Sidecar Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 65 UPS Installation Plan and Unpacking Figure 19. UPS Cabinet with Left or Right-Mounted Sidecar as Shipped on Pallet UPS with Left-Mounted Sidecar UPS with Right-Mounted Sidecar Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 66 UPS Installation Plan and Unpacking Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 67 20. Place a floor protector from the parts kit underneath each jacking bolt, and screw the bolts down against them. The floor protectors protect the floor from being marred by the jacking bolts. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 68 3 mm (1/8") above the floor (just enough to allow the removal of the pallet skids). Failure to follow these instructions can result in serious injury or death. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 69 Sidecar Front Cabinet Support Sidecar Mounting Bolts Sidecar (2 places front) Pallet Skid (2 places rear) Sidecar Skid Mounting Bolts (2 places front) (2 places rear) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 70 Step 23; if using the optional front and rear floor mounting bracket kit, proceed to Step 27; otherwise, proceed to Step 30. 23. Locate the customer supplied left and right side floor mounting brackets and hardware. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 71 Figure 23. Removing the Sidecar Rear Shipping Bracket – UPS with Right-Mounted Sidecar BACK VIEW BACK VIEW (TOP EXHAUST OPTION) (TOP EXHAUST OPTION) REAR SHIPPING BRACKET UPS WITH TOP ENTRY SIDECAR UPS WITH BYPASS SIDECAR (SIAC-B) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 72 Information, for installation instructions. IMPORTANT If the Eaton 93PM-L UPS has a SIAC-B, the Integrated Battery Cabinet must be installed on the opposite side of the UPS away from the SIAC-B. After the IBC is installed, proceed to paragraph 4.4 External AC Power Wiring Installation to complete the wiring of the UPS.
  • Page 73 Route the output cables to the AC Output to Load terminals. Connect phase A, B, and C, and Neutral power wiring from output terminals to the critical load. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 74 (Remove panel to drill or punch conduit holes.) Front Bottom View Top Entry Conduit Landings for Customer Interface Wiring (Remove panels to drill or punch conduit holes.) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 75 AC Input and Output (Remove panel to drill or punch conduit holes.) Bottom Entry Conduit Landing for DC Input (Remove panel to drill or punch conduit holes.) Bottom View Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 76 Inter-cabinet wiring access knockouts. Remove knockouts as required to route power wiring between cabinets. Left Side View Right Side View Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 77 RECTIFIER E9/E10/E11/E12 AC OUTPUT TO LOAD E6/E7/E8/E12 AC INPUT BATTERY INPUT TO BYPASS E5 (-) (2X) GROUND STUDS GROUND FOR CABINET TO COMPRESSION CABINET WIRING LUGS Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 78 AC Input to UPS Bypass Phase B (E7) DC Input from Battery + (E4) Phase A (E6) Cabinet Equipment Grounding Cabinet Bonding Post Conductor Terminals Bonding Post Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 79 Connect phase A, B, and C, and Neutral power wiring from output terminals to the critical load. See paragraph 3.3 UPS System Power Wiring Preparation for wiring and termination requirements. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 80 AC Input and Output (Remove panel to drill or punch conduit holes.) Bottom Entry Conduit Landing for DC Input (Remove panel to drill or punch conduit holes.) Bottom View Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 81 PHASE B (E7) GROUND PHASE C (E8) COMPRESSION BYPASS NEUTRAL (E12) LUGS BATTERY INPUT E4 (+) (2X) GROUND STUDS BATTERY INPUT FOR CABINET TO E5 (-) CABINET WIRING Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 82 Route the output cables to the sidecar AC Output to Load terminals (lower frame area). Connect phase A, B, and C, and Neutral power wiring from output terminals to the critical load. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 83 PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS BATTERY INPUT E4 (+) BATTERY INPUT E5 (-) (2X) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 84 Route the output cables to the sidecar AC Output to Load terminals (lower frame area). Connect phase A, B, and C, and Neutral power wiring from output terminals to the critical load. 10. Proceed to paragraph 4.5 Battery Power Wiring. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 85 PHASE A (E9) PHASE B (E10) PHASE C (E11) GROUND COMPRESSION LUGS BATTERY INPUT E4 (+) BATTERY INPUT E5 (-) (2X) GROUND STUDS FOR CABINET TO CABINET WIRING Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 86 Reinstall all safety shield panels previously removed and secure with the retained hardware. If removed, reinstall the sidecar front panel and secure with the retained hardware. Close the UPS outside door and secure the latch. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 87 Top Entry Wiring. Remove the top interface entry conduit landing plates to drill or punch holes (see Figure Figure 25, or Figure 29). Reinstall the interface entry plates and install the conduit. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 88 15. If wiring additional interface or control wiring options, see Table 20 for next option to install; otherwise, proceed to Step 16. 16. Close the UPS outside door and secure the latch. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 89 Figure 34. Interface Terminal Locations Minislot Interface Terminals Communication Bays Pull Chain and CAN Terminals Cabinet Stiffener Shunt Trip and Auxillary Terminals for Battery and Bypass (CN8 Terminal Block) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 90 RELAY OUTPUT CUSTOMER INPUT ALARMS Figure 36. Bottom Access Interface Wiring Location Wire Tie Anchors Bottom Access Interface Wiring Channel Bottom Entry Conduit Landings for Interface Wiring Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 91 Wires #18 AWG (0.22-0.25 Nm) Building Alarm 3 Return dry contact closure Building Alarm 4 Building Alarm 4 Return Building Alarm 5 Building Alarm 5 Return Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 92 Relay Contact NO Output: General purpose normally-open (NO) relay Relay Contact contact Common Figure 39. Relay Contact Terminal Block Connector Assignments UPS Relay Output NC_Out NO_Out Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 93 MIS - Aux COM MIS - Aux NC 2 lb in Twisted Pair Wires #14 #30 AWG #18 AWG (0.22-0.25 Nm) RIB - Aux COM RIB - Aux NC Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 94: Figure 40. Sidecar Tb1 And Tb2 Terminal Locations

    Aux COM - MBP 2 Aux NC - MBP 3 2 / 3 / 4 Breaker SIAC-B Aux COM - MIS 9 Aux NC - MIS 10 Front of UPS Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 95 15. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. 16. If removed, reinstall the sidecar front panel and secure with the retained hardware. 17. Close the UPS outside door and secure the latch. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 96 Table 20 for next option to install; otherwise, proceed to Step 17. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 97: Figure 41. Bypass Shunt Trip, Battery Shunt Trip And Detect Terminal Detail

    48 Vdc Battery Shunt Trip + 48 Vdc Battery Aux Output: Contacts used to open 1–A battery auxiliary breaker or 48 Vdc Battery Aux disconnect 1–B Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 98 If installing interface wiring connections between standalone cabinets, conduit must be installed between cabinets. NOTE 5 Disconnect terminal block plugs from terminal blocks to wire plugs. To Install wiring: Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 99 Pass-through Wiring. Route the external parallel CAN control wiring between UPS cabinets through the top UPS inter-cabinet wiring access pass-through to the UPS external parallel terminals. See Figure Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 100 External parallel CAN input connections from previous UPS. CAN L In Ground Earth Not Used CAN H Out External parallel CAN output connections to next UPS. CAN L Out Ground Earth Not Used Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 101: Figure 42. External Parallel Can Connections Between Upss

    External parallel CAN connections between UPS cabinets require shielded twisted pair wire with drain wire. NOTE 2 Terminations are 121 ohm 1% resistors installed in the terminal block in the first and last UPS. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 102: Figure 43. External Parallel Terminal Block

    Figure 35 for UPS interface terminal locations. Proceed to Step 15. Bottom Entry Wiring. Remove the bottom interface entry conduit landing plate to drill or punch holes. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 103 17. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. 18. If removed, reinstall the sidecar front panel and secure with the retained hardware. 19. Close the UPS outside door and secure the latch. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 104: Figure 44. External Parallel Pull Chain Wiring

    NOTE 3 Always confirm contact operation prior to wiring. NOTE 4 Any pair of unused building alarm terminals may be used for the MOB Aux 1 connections. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 105 Remove the cabinet stiffener bar (see Figure 34) before installing or removing Minislot cards. Reinstall the bar after the procedure is completed. For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.9 Getting Help). To install wiring: If not already installed, install the LAN drop.
  • Page 106 Remove the bottom interface entry conduit landing plate to drill or punch holes (see Figure 36). 10. Reinstall the interface entry plate and install the conduit. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 107: Figure 45. Repo Switch

    18. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware. 19. If removed, reinstall the sidecar front panel and secure with the retained hardware. 20. Close the UPS outside door and secure the latch. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 108: Figure 46. Repo Terminal Block Connector Assignments

    UPS #18 AWG #30 AWG 4 NO EPO_ EPO from a remote switch Figure 47. Normally-Open REPO Switch Wiring REPO TB REPO Twisted Switch Wires (NO) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 109: Figure 48. Normally-Closed Repo Switch Wiring

    Chapter 10 Warranty for details. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date. 4 4 . . 9 9 C C o o m m p p l l e e t t i i n n g g t t h h e e I I n n s s t t a a l l l l a a t t i i o o n n C C h h e e c c k k l l i i s s t t The final step in installing the UPS system is completing the following Installation Checklist.
  • Page 110 Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional) o Air conditioning equipment is installed and operating correctly. o The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) o Adequate workspace exists around the UPS and other cabinets.
  • Page 111 UPS System Installation Notes _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 112 UPS System Installation Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 113: Figure 49. Main Elements Of The Ups System

    U U P P S S S S y y s s t t e e m m O O v v e e r r v v i i e e w w The Eaton 93PM-L UPS is a continuous-duty, solid-state, transformerless, three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
  • Page 114 5 5 . . 2 2 . . 1 1 M M o o d d e e s s The Eaton 93PM-L UPS supports a critical load in four different modes of operation: • In Energy Saver System (ESS) mode, commercial AC power is supplied directly to the critical load through the internal bypass and transfers automatically to Normal mode (double-conversion on demand) if an abnormal condition is detected.
  • Page 115: Figure 50. Path Of Current Through The Ups In Energy Saver System Mode

    If the UPS suffers an internal failure and is configured for capacity, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 116: Figure 51. Path Of Current Through The Ups In Normal Mode

    UPS automatically attempts to transfer back to Normal mode (up to three times within a ten minute period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to transfer. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 117: Figure 52. Path Of Current Through The Ups In Bypass Mode

    Normal mode. Depending on the total load and the duration of the battery discharge, battery current limit alarms may be seen for a short time due to the current required to recharge the battery. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 118: Figure 53. Path Of Current Through The Ups In Battery Mode

    Bypass Input Switch Output Rectifier Input Rectifier Inverter Rectifier Inverter Switchgear Switchgear Battery Converter Main Power Flow Battery Switchgear Switchgear Trickle Current Closed Energized Open De-Energized Battery Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 119 Top Entry Sidecar Single three UPM reverse transfer UPS Eaton 93PM-L 60 with Figure 56 with internal and/or external battery with Bypass Sidecar (SIAC-B) Bypass Sidecar (SIAC-B) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 120: Figure 54. Eaton 93Pm-L 60 Ups System Oneline

    3. DASHED LINES OUTSIDE OF UPS INDICATE OPTIONAL EQUIPMENT CABINETS. BATTERY 4. BACKFEED PROTECTION IS NOT PROVIDED AS A PART OF UPS. CUSTOMER CABINET SUPPLIED BYPASS INPUT BREAKER WITH 48-60VDC SHUNT TRIP IS REQUIRED. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 121: Figure 55. Eaton 93Pm-L 60 Ups With Top Entry Sidecar System Oneline

    3. DASHED LINES OUTSIDE OF UPS OR TOP ENTRY SIDECAR BOX INDICATE OPTIONAL EQUIPMENT CABINETS. 4. BACKFEED PROTECTION IS NOT PROVIDED AS A PART OF UPS. CUSTOMER SUPPLIED BYPASS INPUT BREAKER WITH 48-60VDC SHUNT TRIP IS REQUIRED. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 122: Figure 56. Eaton 93Pm-L 60 Ups With Bypass Sidecar (Siac-B) System Oneline

    7. THE SINGLE FEED JUMPER (SIAC-B) IS FACTORY INSTALLED WHEN THE UPS IS ORDERED WITH A 4-BREAKER SIDE CAR. THE JUMPER MUST BE REMOVED FOR A DUAL FEED INSTALLATIONS. THE 4-BREAKER SIDE CAR IS ONLY AVAILABLE WITH A DUAL FEED UPS. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 123: Figure 57. Ups Controls And Indicators

    UPS operation, see paragraph 6.2 Using the Control Panel. Figure 57. UPS Controls and Indicators CONTROL PANEL DOOR LATCH Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 124: Figure 58. Ups Control Panel

    The four symbols on the bottom of the control panel are status indicators. These colored light emitting diode (LED) lamps work with the alarm horn to provide the operating status of the UPS. Table 29 describes the status indicators. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 125 All functions and commands are accessed by touching or tapping the screen tabs or buttons. When text input is required, either a Qwerty keyboard or numeric keypad will be displayed. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 126: Figure 59. Parts Of The Lcd

    The UPS navigation tab menu bar allows you to display data in the information area to help you monitor and control UPS operation. Table 30 shows the basic menu structure. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 127: Figure 60. Main Menu And Mimic Screen

    The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation of the operating status of the system. Figure 60. Main Menu and Mimic Screen Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 128 The end of the log (the most recent events) is displayed first; scroll upward to view older event listings. To scroll through the events, press the up or down scroll bar. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 129: Figure 61. Typical Meters Summary Screen

    Statistics Details Tap the desired statistic button to display the detailed statistic screen. Controls See paragraph 6.2.8 System Controls for details. Figure 61. Typical Meters Summary Screen Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 130: Figure 62. Typical Active Events Screen

    UPS Operating Instructions Figure 62. Typical Active Events Screen Figure 63. Typical System Log Screen Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 131: Figure 64. Typical Settings User Screen

    UPS Operating Instructions Figure 64. Typical Settings User Screen Figure 65. Typical Information Screen Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 132: Figure 66. Typical About Screen

    UPS Operating Instructions Figure 66. Typical About Screen Figure 67. Typical Settings Configuration 1 Screen Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 133: Figure 68. Typical Settings Configuration 2 Screen

    6 6 . . 2 2 . . 7 7 S S i i g g n n I I n n The Controls and Setting screens are restricted. The user must sign in using a password to gain access. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 134: Figure 70. Sign In Password Screen

    Level 1 default password is 1111. Settings Level 2 default password is 0101. Sign in is complete. Tap continue to return to previous screen. Figure 70. Sign In Password Screen Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 135: Figure 71. Sign In Keypad

    Bypass mode from Double Conversion mode. Charger TURN ON CHARGER/TURN OFF CHARGER sets the battery charger on or off. Battery Test RUN BATTERY TEST starts the battery test. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 136: Figure 72. Typical System Control Screen

    Table 33. Typical System Status Messages Message Function Double Conversion; Bypass; ESS Bypass Off; On; Available Charger Charger Resting; Charger Figure 72. Typical System Control Screen Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 137: Figure 73. Typical Ups Control Screen

    UPS Operating Instructions Figure 73. Typical UPS Control Screen Figure 74. Typical UPM Select Screen Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 138: Figure 75. Typical Upm Control Screen

    UPS Operating Instructions Figure 75. Typical UPM Control Screen Figure 76. Typical EAA Control Screen Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 139 Verify no alarms are active. Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed. Tap the GO TO BYPASS button. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 140 6 6 . . 3 3 . . 5 5 T T r r a a n n s s f f e e r r f f r r o o m m D D o o u u b b l l e e C C o o n n v v e e r r s s i i o o n n t t o o B B y y p p a a s s s s M M o o d d e e To transfer the critical load to Bypass mode: Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 141 6 6 . . 3 3 . . 9 9 T T r r a a n n s s f f e e r r f f r r o o m m D D o o u u b b l l e e C C o o n n v v e e r r s s i i o o n n t t o o B B y y p p a a s s s s M M o o d d e e a a n n d d S S h h u u t t D D o o w w n n U U P P M M s s To transfer the critical load to Bypass mode and shut down the UPMs: Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 142 To perform maintenance or service on the critical load, shut down power to the load: Turn off all equipment that is being powered by the UPS. Perform the Load Off procedure in paragraph 6.3.15 Using the UPS LOAD OFF Command. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 143 The UPS (including Bypass) remains off until restarted. To use the LOAD OFF command: Tap the CONTROLS tab on the main menu navigation bar. The System Control screen is displayed. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 144 Firmly push the red pushbutton until it locks into place. The switch latches into the activated state (see Figure 77). The rectifier, inverter, and battery switchgear open, and the power module is turned off immediately, without asking for verification. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 145: Figure 77. Repo Operation

    6 6 . . 4 4 . . 1 1 S S t t a a r r t t i i n n g g t t h h e e P P a a r r a a l l l l e e l l S S y y s s t t e e m m i i n n D D o o u u b b l l e e C C o o n n v v e e r r s s i i o o n n M M o o d d e e To start the UPS system: Close all Module Output Breakers (MOBs). Close the UPS input feeder circuit breaker. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 146 Tap the MODULES CONTROLS tab on the secondary Control menu navigation bar. The UPM Select screen is displayed. On the UPM Select screen, select UPM 1. The UPM Control Screen is displayed. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 147 6 6 . . 4 4 . . 6 6 T T r r a a n n s s f f e e r r f f r r o o m m B B y y p p a a s s s s t t o o D D o o u u b b l l e e C C o o n n v v e e r r s s i i o o n n M M o o d d e e To transfer the critical load to Normal mode: Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 148 Logic power remains on. Repeat Step 2 through Step 5 selecting UPM 3 to shutdown UPM 3. The UPM status indicates SHUTDOWN. The power module is turned off. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 149 To restart a single UPS from a shutdown state: Close the MOB for the UPS being restarted. Close the UPS input feeder circuit breaker for the UPS being restarted. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 150 Tap the UPS CONTROLS tab on the secondary navigation bar. The UPS Control screen is displayed. Tap the TURN ON CHARGER button. To turn the battery charger off: Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 151 Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 152 Power is present inside the UPS cabinet until the upstream input feeder circuit breakers and battery breakers are opened. Wait at least 5 minutes before accessing internal components. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 153: Figure 78. Optional Minislot Cards

    IRC-MS installation guide. One input can be activated by a switch or dry contact. The voltage source is provided by the card, no external voltage source is needed. For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.9 Getting Help).
  • Page 154 It’s also powered by CA Technologies, bringing together the best in hardware and software. PredictPulse Service is included at no charge during the first year of Eaton 93PM-L UPS operation (warranty period) along with the required connectivity parts. Beyond that, it may be purchased with Eaton Support Agreements or as a standalone subscription after the initial warranty expires.
  • Page 155 Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
  • Page 156 Communication Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 157 The UPS system requires very little preventive maintenance. However, the system should be inspected periodically to verify that the units are operating normally and that the batteries are in good condition. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 158 The foam filters are to be replaced with new or washed filter immediately. The ups is not meant to be run without filters installed. Close the front door and secure the latch. Record maintenance results and any corrective actions in a suitable log. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 159: Figure 79. Air Filter Location

    8 8 . . 2 2 . . 4 4 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings.
  • Page 160 Phillips and Pozidriv are registered trademarks of Phillips Screw Company. A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system Copyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 161 9 9 . . 2 2 . . 2 2 U U P P S S O O u u t t p p u u t t UPS Output Capacity 100% rated current Output Voltage Regulation ± 1% (10% to 100% load) Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 162 Meets IEC 61000-4-2 Level 3 specifications and CISPR 24. Withstands up to 4 kV (ESD) contact pulse without damage and with no disturbance or adverse effect to the critical load. Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 163 For warranty information, please refer to the Resources link on our website, www.eaton.com/93PM. EQUIPMENT REGISTRATION Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory. Model Number: Serial Number: Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03...
  • Page 164 P-16400071103 P-164000711 03...