UPS OPERATING INSTRUCTIONS
9.6

Transferring to Bypass and Shutting Down the UPS

9.7

Shutting Down the UPS and Critical Load

9.8

Using the UPS Emergency UPM Off Pushbutton

9-6
EATON Powerware
To transfer the critical load to Bypass mode and shut down the UPS:
1.
On the UPS, turn the Mode key switch to BYPASS for one second.
2.
Confirm UPS breaker CB4 closes and UPS breaker CB3 opens.
The UPS switches to Bypass mode. If the bypass source is not available, the
power processor unit remains on and an alarm sounds.
On the UPS LCD screen, verify that the On Bypass message appears and the
3.
BYPASS Mode indicator illuminates on the control panel
on bypass.
4.
On the UPS, turn the Mode key switch to BYPASS for one second.
5.
Observe that UPS breaker CB1 and Battery Disconnect CB2 open.
The bypass source supplies the critical load, the power processor unit
de-energizes and cooling blowers shutdown.
Power is present at the UPS breaker CB1 input, until the upstream UPS input feeder circuit breaker is
opened.
To perform maintenance or service on the critical load, shut down power to the load:
1.
Transfer the critical load to bypass by performing the procedure in paragraph 9.4.
2.
Turn off all equipment that is being powered by the UPS.
3.
Press the Emergency UPM Off pushbutton on the control panel.
Power is present at the UPS breaker CB1 input, until the upstream UPS input feeder circuit breaker is
opened.
4.
Open the UPS input feeder circuit breaker.
Initiate a UPS Emergency UPM Off using the covered, red Emergency UPM Off
pushbutton on the UPS control panel. This pushbutton is protected by a clear plastic
shield to prevent accidental activation. In an emergency, you can press this
pushbutton to instantaneously control the UPS output. The UPS Emergency UPM Off
pushbutton functions differently, depending on the Emergency Power-off option
specified when ordered. The options available are as follows:
S
Power to the critical load is de-energized and the UPS powered down. UPS
breakers CB1, CB3, FBP, and Battery Disconnect CB2 trip, and the UPS is cut off
from utility power.
S
The critical load is transferred to bypass and the UPS powered down. UPS
breakers CB1, CB3, and Battery Disconnect CB2 trip, and the UPS is cut off from
utility power.
®
9315 UPS (500–750 kVA) Installation and Operation Manual
.
The UPS system is now
W A R N I N G
W A R N I N G