Powerware is a registered trademark and ConnectUPS is a trademark of Eaton Corporation. ECopyright 2004−2007 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
(optional) requires (optional) 480/208 transformer) Figure 1-1. Typical Powerware 9315 UPS System These basic UPS system configurations are possible: The UPS and one or more battery cabinets The UPS, battery cabinet(s), and a Power Distribution Module (PDM) The UPS, battery cabinet(s), and an input cabinet (transformer or filter)
In this manual, the term UPS" refers only to the UPS cabinet and its internal elements. The term UPS system" refers to the entire power protection system – the UPS modules, battery strings, and options or accessories installed. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 1−2 EATON Powerware ®...
If you need to schedule initial startup, need regional locations and telephone numbers, have a question about any of the information in this manual, or have a question this manual does not answer, please call the Eaton Help Desk for Powerware products at:: In the United States...
Page 8
Introduction This page intentionally left blank. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 1−4 EATON Powerware ®...
NOTE Startup and operational checks should be performed only by authorized service personnel. This service is usually offered as part of the sales contract for your UPS system. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 2−1 EATON Powerware ®...
For your UPS system to operate at peak efficiency, the installation site should meet the environmental specifications outlined in the Powerware 9315 (300–500 kVA) UPS Operation Manual. If you intend to operate the UPS at an altitude higher than 1500m (5000 ft), contact your service representative for important information about high altitude operation.
25 mm (1″). 6. Remove the plastic bag and foam packing material, and discard or recycle them in a responsible manner. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 2−3 EATON Powerware ®...
Page 12
Getting Started This page intentionally left blank. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 2−4 EATON Powerware ®...
The UPS cabinet is bolted to a sheet metal pallet consisting of four supports secured to foam cushions. The foam cushions act as shock absorbers for the cabinet during shipment and movement to the installed location. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 3−1 EATON Powerware ®...
4. Insert the forklift jacks in the forklift slots and raise the UPS cabinet until the cabinet bottom clears the foam cushions by approximately 3 mm (1/8″). 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 3−2 EATON Powerware ®...
6. Carefully lower the cabinet until the UPS cabinet base contacts the floor. 7. Repeat Steps 1 through 6 for each cabinet you are preparing to install. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 3−3 EATON Powerware ®...
UPS cabinet for wiring these options. See Figure 3-3 for the location of the interface points within the UPS cabinet. Also, refer to the Powerware 9315 Series 685 and 1085 Auxiliary Battery Cabinets Installation Manual for information on installing battery cabinets.
NOTE A bypass neutral feeder must be supplied when the output neutral is used. If no bypass neutral is supplied, the output neutral is to be bonded to ground through a minimum 3/0 copper conducter. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 3−5 EATON Powerware ®...
NOTE The installation checklist MUST be completed before starting the UPS system for the first time. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 3−6 EATON Powerware ®...
- A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the UPS and battery cabinet. (OPTIONAL) - Circuit breakers with adjustable trip mechanisms adjusted to match site requirements. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 3−7 EATON Powerware ®...
This chapter describes installing the UPS manufacturer’s battery cabinets. If you are installing battery cabinets and remote disconnects provided by Powerware, refer to the Powerware 9315 Series 685 and 1085 Auxiliary Battery Cabinets Installation Manual for instructions. One model is available: the Series 1085 (1085−mm wide cabinet).
Page 22
If you are installing battery cabinets not provided by Powerware, refer to the battery cabinet manufacturer’s operating manual for instructions on battery cabinet installation and maintenance. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 4−2 EATON Powerware ®...
Figure 5-1 through Figure 5-4. See Appendix A for cabinet dimensions. Customer Input Area (Top) Top View Front View Figure 5-1. Input Transformer Cabinet (480/480V and 600/480V) 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 5−1 EATON Powerware ®...
Installing Input and Output Transformers and Input Filter Cabinets Customer Input Area (Top) Top View Front View Figure 5-4. Output Transformer Cabinet (480/208V) 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 5−4 EATON Powerware ®...
Page 27
3. Connect the cables as shown in Table B on page A−3 and Table E on page A−6. See Figure 5-5 through Figure 5-7 for location of connection points within the cabinets. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 5−5 EATON Powerware ®...
Page 28
Table 5-4. Output Transformer Connection Points Connection Point in Transformer Cabinet Connection point in UPS Phase Input Output ∅ A ∅ B ∅ C Neutral 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 5−6 EATON Powerware ®...
4. Close the UPS cabinet doors and the output transformer cabinet door. AC Input AC Output to Transformer to UPS Ground Front Figure 5-5. Installing a 480/480 Vac or 600/480 Vac Input Transformer Cabinet 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 5−7 EATON Powerware ®...
Installing Input and Output Transformers and Input Filter Cabinets AC Input AC Output to Transformer to UPS Ground Front Figure 5-6. Installing a 480/480 Vac Input Filter Cabinet 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 5−8 EATON Powerware ®...
Installing Input and Output Transformers and Input Filter Cabinets AC Output Output AC Input to UPS Input Neutral to Transformer Neutral Front Figure 5-7. Installing a 208/480 Vac Input Transformer Cabinet 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 5−9 EATON Powerware ®...
Installing Input and Output Transformers and Input Filter Cabinets AC Input to Transformer AC Output to UPS Ground Neutral Front Figure 5-8. Installing a 480/208 Vac Output Transformer Cabinet 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 5−10 EATON Powerware ®...
Distribution Module Installation and Operation Manual for PDM installation and operation. NOTE This option requires a 480 to 208 Vac transformer. Figure 6-1. Typical PDM Cabinet 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 6−1 EATON Powerware ®...
Page 34
Installing a Power Distribution Module This page intentionally left blank. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 6−2 EATON Powerware ®...
Figure 7-2. Remote EPO switch wiring must be in accordance with UL Class II requirements. 6. Secure the UPS by reversing all steps taken to prepare it for Remote EPO installation. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 7−2 EATON Powerware ®...
3 (UV trip) must be connected to the DC source disconnect device(s). For battery switch dimensions, see Drawing 164201118−13 on page A−41. Side Front Figure 8-1. Remote Battery Disconnect Enclosure 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 8−1 EATON Powerware ®...
Installing a Remote Monitor Panel Flush Mount Surface Mount (for Hanging) Wires Must be Twisted Figure 9-1. Remote Monitor Panel 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 9−2 EATON Powerware ®...
Communication Panel. Connect to Port 1 (DB−9) on Communication Panel Fuse Terminal Block (TB3) Figure 9-2. Terminal Block Bracket 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 9−3 EATON Powerware ®...
If this does not correct the problem, contact your service representative for verification that the RMP is working correctly. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 9−4 EATON Powerware ®...
Page 43
8. If you are installing an RIM or SCM in addition to an RMP, proceed to Chapter 10 or 11, respectively; otherwise, secure the UPS cabinet by reversing the steps on page 3−4. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 9−5 EATON Powerware ®...
Page 44
Installing a Remote Monitor Panel This page intentionally left blank. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 9−6 EATON Powerware ®...
DB−9 connector on the Communication Panel of the UPS (see Figure 10-3). Use two screws from the spare parts kit to secure the terminal block bracket to the Communication Panel. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 10−1 EATON Powerware ®...
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Figure 10-3. Wiring an RIM to the UPS 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 10−2 EATON Powerware ®...
Page 47
TB1−7 TB3−4 From RIM B (if used) To UPS Remarks TB1−4 TB3−5 TB1−5 TB3−6 Twisted wires (4) 1−2 turns per 3″ TB1−6 TB3−7 TB1−7 TB3−8 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 10−3 EATON Powerware ®...
Page 48
Installing a Relay Interface Module This page intentionally left blank. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 10−4 EATON Powerware ®...
DB−9 connector on the Communication Panel of the UPS (see Figure 11-3). Use two screws from the spare parts kit to secure the terminal block bracket to the Communication Panel. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 11−1 EATON Powerware ®...
5. Contact your service representative for verification and testing of the SCM and its connections prior to making connections to terminal strip shown in Figure 11-4. 6. Repeat Steps 1 through 5 for each SCM you are installing. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 11−2 EATON Powerware ®...
Page 51
TB1−7 TB3−4 From SCM B (if used) To UPS Remarks TB1−4 TB3−5 TB1−5 TB3−6 Twisted wires (4) 1−2 turns per 3″ TB1−6 TB3−7 TB1−7 TB3−8 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 11−3 EATON Powerware ®...
NOTE Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc. NOTE Supervisory contacts require external power supply. Internal 24 Vdc is not capable of supplying contact current. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com 11−4 EATON Powerware ®...
Remote Emergency Power Off 164201118−10 Remote Monitor Panel 164201118−11 Relay Interface Module 164201118−12 Supervisory Contact Module 164201118−13 Battery Disconnect Switch 164201118−14 Compression Lug Kit Option 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−1 EATON Powerware ®...
Page 54
Customer Information Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9315 400 (0.8 pF) Units Rating 50/60 Hz Ratings Basic unit rating at 0.8 lagging pF load INPUT/OUTPUT VOLTAGE AC Input to UPS Rectifier (0.95 min. pF) With Filter:...
Page 55
Customer Information Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9315 500 (0.8 pF) Units Rating 60 Hz Ratings Basic unit rating at 0.8 lagging pF load INPUT/OUTPUT VOLTAGE AC Input to UPS Rectifier or Input Transformer With Filter: (0.95 min.
Page 56
Customer Information Table C. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9315 400 (0.9 pF) Units Rating 50/60 Hz Ratings Basic unit rating at 0.9 lagging pF load INPUT/OUTPUT VOLTAGE AC Input to UPS Rectifier (0.95 min. pF) With Filter:...
Page 57
Customer Information Table D. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9315 500 (0.9 pF) Units Rating 60 Hz Ratings Basic unit rating at 0.9 lagging pF load INPUT/OUTPUT VOLTAGE AC Input to UPS Rectifier or Input Transformer With Filter: (0.95 min.
Page 59
NOTE: Customer ground, size 2/0, can be run in any conduit listed in Table H. DRAWING NO: SHEET: 6 of 19 164201118−1 REVISION: D DATE: 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−7 EATON Powerware ®...
Page 60
NOTE: Customer ground, size 2/0, can be run in any conduit listed in Table H. DRAWING NO: SHEET: 164201118−1 7 of 19 REVISION: D DATE: 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−8 EATON Powerware ®...
Page 62
(A, B, C, Gnd) Battery 2.5 in. 2.5 in. (+), (−), Gnd DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201118−1 9 of 19 REVISION: DATE: 041500 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−10 EATON Powerware ®...
Page 63
3/8 inch (9.5 mm) diameter. Minimum of five wraps. 6 inches (152 mm) DESCRIPTION: INSTALLATION NOTES 164201118−1 DRAWING NO: SHEET: 10 of 19 REVISION: D DATE: 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−11 EATON Powerware ®...
Page 64
UPS. Table I lists the ventilation requirements for full load operation: Table I. Air Conditioning or Ventilation Requirements During Full Load Operation Heat Rejection* Ratings BTU/hr 1000/hr (Kg−cal/hr) Input/Output Voltage 0.8 pF 0.9 pF Powerware 9315 400 300 kVA 400/400 71.7 (18.1) 81.0 (20.4) 400 kVA 400/400 95.6 (24.1) 107.9 (27.2)
Page 65
The input breaker (CB1) has a trip rating of 1000 amps AT and an Amp Interrupting Capability (AIC) of 65,000 in symmetrical RMS amps for the Powerware 9315 400 and 9315 500. See Table K. Table K. Equivalent Transformer Size for Determining Inrush...
Page 66
Output overcurrent protection and output disconnect switch are to be provided by the user. Table L lists the maximum rating for output circuit breakers satisfying the criteria for both. Table L. Maximum Output Circuit Breaker Ratings Output Voltage Rating Powerware 9315 System 208V 400V 480V...
Page 67
Table N, according to your UPS system configuration: Table N. Equipment Weight Weight (Kg (lb) Component Shipping Installed UPS Cabinet (Powerware 9315 400) 2812 (6200) 2767 (6100) (400/400 System) UPS Cabinet (Powerware 9315 500) 2812 (6200) 2767 (6100)
Page 68
Panel. Use twisted pair wires for each alarm input and common. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201118−1 15 of 19 REVISION: G DATE: 020604 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−16 EATON Powerware ®...
Page 69
RELAY 2 NC General purpose NO and NC relay contacts. NOTICE RTN DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 16 of 19 164201118−1 REVISION: G DATE: 020604 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−17 EATON Powerware ®...
Page 70
CONTACT RATING: Maximum Switched Voltage 32 VAC 42 VDC Maximum Carrying Current DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 17 of 19 164201118−1 REVISION: G DATE: 020604 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−18 EATON Powerware ®...
Page 71
NOTE: This switch must be a dedicated switch not tied into any other circuits. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 18 of 19 164201118−1 REVISION: D DATE: 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−19 EATON Powerware ®...
Page 72
NOTE: For other than Powerware battery cabinets that use UV trip coils, connect to TB4 Pin 3 instead of TB4 Pin 2. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 19 of 19 164201118−1 REVISION: D DATE: 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−20 EATON Powerware ®...
Page 73
(optional) (Transformer or (optional− Filter) (optional) requires (optional) 480/208 transformer) DESCRIPTION: TYPICAL UPS SYSTEM DRAWING NO: SHEET: 164201118−2 1 of 1 REVISION: C DATE: 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−21 EATON Powerware ®...
Page 75
DRAWING NO: SHEET: 164201118−4 1 of 5 neutral is to be bonded to ground through a REVISION: F DATE: minimum 3/0 copper conducter. 082806 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−23 EATON Powerware ®...
Page 76
3/0 copper conducter. DRAWING NO: SHEET: 164201118−4 2 of 5 NOTE 2: See Figure 164201118−3 to determine REVISION: F DATE: 082806 when an input transformer is required. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−24 EATON Powerware ®...
Page 77
3/0 copper conducter. DRAWING NO: SHEET: 164201118−4 3 of 5 NOTE 2: See Figure 164201118−3 to determine REVISION: F DATE: when an input transformer is required. 082806 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−25 EATON Powerware ®...
Page 78
3/0 copper conducter. DRAWING NO: SHEET: 164201118−4 4 of 5 NOTE 2: See Figure 164201118−3 to determine REVISION: F DATE: 082806 when an input transformer is required. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−26 EATON Powerware ®...
Page 79
3/0 copper conducter. DRAWING NO: SHEET: 164201118−4 5 of 5 NOTE 2: See Figure 164201118−3 to determine REVISION: F DATE: 082806 when an input transformer is required. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−27 EATON Powerware ®...
Page 80
I/O SECTION PANEL RS−232 (E9, E10, E11) WIREWAY CONNECTION DESCRIPTION: LOCATION OF UPS POWER TERMINALS DRAWING NO: SHEET: 164201118−5 1 of 1 REVISION: G DATE: 020604 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−28 EATON Powerware ®...
Page 81
Customer Information DESCRIPTION: UPS CABINET DRAWING NO: SHEET: 164201118−6 1 of 2 REVISION: A DATE: Dimensions are in millimeters (inches) 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−29 EATON Powerware ®...
Page 82
Customer Information DESCRIPTION: UPS CABINET DRAWING NO: SHEET: 164201118−6 2 of 2 REVISION: A DATE: 010198 Dimensions are in millimeters (inches) 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−30 EATON Powerware ®...
INPUT ISOLATION TRANSFORMER CABINET (480/480 and 600/480) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201118−7 1 of 4 REVISION: D DATE: Dimensions are in millimeters (inches) 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−31 EATON Powerware ®...
Page 84
(47.2) 5% INPUT FILTER CABINET (480/480) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201118−7 2 of 4 REVISION: D DATE: Dimensions are in millimeters (inches) 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−32 EATON Powerware ®...
Page 85
(47.2) INPUT ISOLATION TRANSFORMER CABINET (208/480) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201118−7 3 of 4 REVISION: D DATE: Dimensions are in millimeters (inches) 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−33 EATON Powerware ®...
Page 86
(47.2) OUTPUT AUTO TRANSFORMER CABINET (480/208) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201118−7 4 of 4 REVISION: D DATE: Dimensions are in millimeters (inches) 101598 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−34 EATON Powerware ®...
Page 87
15−100A 2- and 3-Pole; 125A, 2-Pole. Grounding Grounding Stud Stud DESCRIPTION: POWER DISTRIBUTION MODULE DRAWING NO: SHEET: 164201118−8 1 of 1 REVISION: A DATE: 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−35 EATON Powerware ®...
Page 88
TO OTHER TO UPS EQUIPMENT DESCRIPTION: REMOTE EMERGENCY POWER OFF DRAWING NO: SHEET: 164201118−9 1 of 1 Dimensions are in millimeters (inches) REVISION: A DATE: 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−36 EATON Powerware ®...
Page 89
(14−18 gauge) EXCEED 500 FEET. DESCRIPTION: REMOTE MONITOR PANEL DRAWING NO: SHEET: 164201118−10 1 of 1 REVISION: A DATE: Dimensions are in millimeters (inches) 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−37 EATON Powerware ®...
Page 90
MIN WIRE SIZE NO. 18 AWG. DESCRIPTION: RELAY INTERFACE MODULE DRAWING NO: SHEET: 164201118−11 1 of 2 Dimensions are in millimeters (inches) REVISION: A DATE: 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−38 EATON Powerware ®...
Page 91
KNOCKOUTS PROVIDED ON FIVE SURFACES DESCRIPTION: RELAY INTERFACE MODULE DRAWING NO: SHEET: 164201118−11 2 of 2 Dimensions are in millimeters (inches) REVISION: A DATE: 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−39 EATON Powerware ®...
Page 92
REMOTE MONITOR AND UPS NOT TO EXCEED 500 FEET. DESCRIPTION: SUPERVISORY CONTACT MODULE DRAWING NO: SHEET: 164201118−12 1 of 1 REVISION: A DATE: Dimensions are in millimeters (inches) 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−40 EATON Powerware ®...
Page 93
KNOCKOUTS TO BE DETERMINED AT 75 LBS (34 KG) TIME OF INSTALLATION. DESCRIPTION: BATTERY DISCONNECT SWITCH DRAWING NO: SHEET: 164201118−13 1 of 2 REVISION: A DATE: 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−41 EATON Powerware ®...
Page 94
Customer Information TYPE K1200 BREAKER OUTLINE DESCRIPTION: BATTERY DISCONNECT SWITCH DRAWING NO: SHEET: 164201118−13 2 of 2 REVISION: A DATE: 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−42 EATON Powerware ®...
Page 95
Thomas & Betts TBM14M Crimp Tool Die Set Thomas & Betts 15514 DESCRIPTION: BATTERY DISCONNECT SWITCH DRAWING NO: SHEET: 164201118−14 1 of 1 REVISION: A DATE: 010198 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−43 EATON Powerware ®...
Page 96
Customer Information This page intentionally left blank. 9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com A−44 EATON Powerware ®...