Cisco 6513 - Catalyst Switch Installation Manual page 60

Installation guide
Hide thumbs Also See for 6513 - Catalyst Switch:
Table of Contents

Advertisement

Catalyst 6509-NEB-A Switch
Table 1-18 Catalyst 6509-NEB-A Switch Specifications
Item
Environmental
Temperature, operating
Temperature, nonoperating
and storage
Thermal transition
Humidity (RH), ambient
(noncondensing) operating
Humidity (RH), ambient
(noncondensing)
nonoperating and storage
Altitude, operating
Physical Characteristics
Dimensions (H x W x D)
Weight
Airflow
Catalyst 6500 Series Ethernet Modules Installation Guide
1-44
Specification
Certified for operation: 32° to 104°F (0° to 40°C)
Designed and tested for operation: 32° to 130°F (0° to 55°C)
The Catalyst 6500 series switches are equipped with internal air
Note
temperature sensors that are triggered at 104°F (40°C) generating a
minor alarm and at 131°F (55°C) generating a major alarm.
–4° to 149°F (–20° to 65°C)
0.5°C per minute (hot to cold)
0.33°C per minute (cold to hot)
10% to 90%
5% to 95%
Certified for operation: 0 to 6500 feet (0 to 2000 m)
Designed and tested for operation: –200 to 10,000 feet (–60 to 3000 m)
36.7 x 17.2 x 20.3 in. (93.1 x 43.7 x 51.6 cm).
Chassis requires 21 RU.
Chassis can be mounted in equipment racks that meet ANSI/EIA 310-D
and ETS 300-119 standards.
Chassis only: 121 lb (54.9 kg).
Chassis fully configured with 1 supervisor engine, 8 modules, 2 AC-input
power supplies: 270 lb (122.47 kg).
FAN-MOD-09 (high-speed fan tray)—760 CFM
To maintain proper air circulation through the Catalyst switch
Note
chassis, we recommend that you maintain a minimum 6-inch (15 cm)
separation between a wall and the chassis air intake or a wall and the
chassis air exhaust. You should also allow a minimum separation of
12 inches (30.5 cm) between the hot air exhaust on one chassis and
the air intake on another chassis. Failure to maintain adequate air
space can cause the chassis to overheat and the system to fail. On
Catalyst chassis in which the airflow is from front to back, the
chassis may be placed side-by-side.