Hardware Installations and Upgrades
number of units installed in the rack. Consideration of the units' nameplate rating
should be used when addressing these concerns.
The electrical distribution system must provide a reliable earth for each unit and the
rack.
Each storage system has an earth leakage current of 0.75 mA. The design of the
electrical distribution system must take into consideration the total earth leakage
current from all the power supplies in all the units. The rack will require labelling with
"HIGH LEAKAGE CURRENT. Earth connection essential before connecting
supply."
The rack when configured with the units must meet the safety requirements of UL
60950-1 and IEC 6095-10.

Rack Mount Rail Kit

A set of mounting rails is available for use in 19-in rack cabinets. These rails have been
designed and tested to handle the maximum enclosure weight and to ensure that multiple
enclosures may be installed without loss of space within the rack. Use of other mounting
hardware may cause some loss of rack space.
Assembling the Rail Kit
Please refer to the Rail Kit Install Guide: Intel
Storage System SSR212CC supplied with the rack mounting rail kit for assembly details.

Removing or Installing the Enclosure Cover

Warning: The enclosure cover must only be removed by a service personnel. Potential hazards
include:
Energy hazard
Rotating fans
Hot surfaces
Access to power supply unit openings
Upon replacement, the cover MUST be secured by tightening the retaining screw with a
screwdriver.

Removing the Enclosure Cover

Important: The cover should only be removed by service personnel as it provides access to a service
area.
1. Observe all safety and ESD precautions listed in
14
®
Storage System SSR212MA/Intel®
Appendix D, "Safety
Intel® Storage System SSR212CC User Guide
Information".