Download Print this page

Danfoss VACON 1000 Operating Manual page 150

Hide thumbs Also See for VACON 1000:

Advertisement

Operating Guide | VACON® 1000
Table 30: Technical Data for
(continued)
Output
150
| Danfoss A/S © 2024.12
Output voltage range
Output current THDi (1st...49th)
Output dU/dt
Output frequency range
Loading
Motor type
Power factor
System efficiency
Overload capacity
Start-up torque
Frequency resolution
Speed control range
Steady state speed control accuracy
(% of rated speed)
Speed response bandwidth
Current response bandwidth
Switching frequency of the power
cells
Design operating time
Minimum availability per 12
months
Product lifetime
2.4–11 kV
<2% at rated speed
<3000 V/µs
0–75 Hz (higher frequencies, for example, 120 Hz can be evalu-
ated)
Squared torque
Constant torque
Constant torque and/or power
Induction (asynchronous) motor
Synchronous motor (with separate excitation)
>0.96 (at rated load)
• at 25% load: 0.9562
• at 50% load: 0.9633
• at 75% load: 0.9675
• at 100% load: 0.966
>98.5% (at rated load, excluding transformer)
>96.5% (at rated load, including transformer)
• at 25% load: 95.59%
• at 50% load: 96.73%
• at 75% load: 96.78%
• at 100% load: 96.5%
110% for 1 min every 10 min (variable torque applications)
150% for 1 min every 10 min (constant torque applications)
For other overload capacity requirements, contact .
>120% rated torque
If higher start-up torque is required, contact .
0.01 Hz
1–100% (with Closed-loop Vector Control)
5–100% (with Sensorless Vector Control)
±0.01% (with Closed-loop Vector Control, depending on sensor
accuracy)
±0.5% (with Sensorless Vector Control)
60 rad/s (with closed loop control)
20 rad/s (with sensorless control)
600 rad/s
Default: 600 Hz
Maximum: 1200 Hz
24 hours/day
99.97%
20 years
Specifications
AQ363633621020en-000401 / 172F3117D

Advertisement

loading
Need help?

Need help?

Do you have a question about the VACON 1000 and is the answer not in the manual?