3. GENERAL DESCRIPTION
Internet/Intranet
Web-server
The web-server II is used when one c.i.e. or a system with two or more c.i.e. in a TLON Network shall be
connected to Internet/Intranet (LAN), to a Security Management System and/or as a Gateway. The unit can
be used:
• For presentation of actual c.i.e status in a computer using the web browser. It can also send e-mail
in case of pre-warning, fire alarm, fault, disablement, test mode alarm, and/or service signal.
• For remote control and two-way communication. Ten different users and three access levels.
• As a gateway to other computer systems. The following alternatives are available today:
o EBLTalk (RS232 or TCP/IP) is an open protocol, used to transmit and present fire alarm
information in a separate computer / system.
o ESPA 4.4.4 (RS232) used to transmit and present fire alarm information in a paging
system.
o SIA (RS232) used to transmit and present fire alarm information in a separate computer
application.
o MODBUS (RS232 or TCP/IP) used to transmit and present fire alarm information in a
separate computer application.
• As a gateway to a security management system via EBLNet (TCP/IP). EBLNet license is required.
TECHNICAL DESCRIPTION 1598 • DOCUMENT NUMBER: MEW01930 • REVISION: 4
EBL512 G3
c.i.e.
RS232
7
EBL512 G3 system
EBL512 G3
c.i.e.
TLON Network