10. EBLWEB
OUTPUT ACTIVATION
In case of forced output activations, press the List button
The Time (date & time), c.i.e., Exp.Board, Loop, and Address are displayed.
Output = The output number.
Press the De-activate button in the de-activate column for a pop-up dialog for de-activation of the force
activated output. (Requires login on User level 2 or 3.)
WEB FUNCTION DISABLEMENT (WEB STATUS)
In case of any WEB-function disablement, press the WEB function LED button
view the WEB function disablement list.
This view shows the current status of disablement of WEB functions, such as E-mails, PC-buzzer, and
Gateway. It also shows the time-stamp for previous login and current EBLWeb software version.
10.4.10.
COMMUNICATION ERROR
In case of any communication error, press on the Communication error LED button
to view the communication error list.
This view shows the current communication state for several kinds of communication errors as listed. If in
error state, the state will be 'blinking' Error, otherwise a steady Normal will be shown.
EBL - WEB
Communication between CU and
WEB-server.
WEB - Browser
Communication between WEB-
server and browser
E-mail SMTP - WEB
Communication between SMTP-
server and WEB-server
WEB - Gateway
Communication between WEB-
server and current configured
Gateway function.
TECHNICAL DESCRIPTION 1598 • DOCUMENT NUMBER: MEW01930 • REVISION: 4
to view the output activation list.
Could be a problem with the serial
cable between the WEB-server and
the CU or incompatible SW versions
(e.g. CU is running version 2.1.x and
WEB-server is running version 2.5.x).
Normally no TCP/IP connection with
WEB-server from browser.
Normally no access to SMTP server.
No e-mail can be sent.
Normally no replies/ACK from the
gateway device.