6. CONFIGURATION OF EBLWEB
6.1.5.

GATEWAY/EBLNET SETTINGS

The EBLWeb is not only a web-server but can also be a gateway to another system.
One of the following gateway types can be selected:
None: No gateway function will be used.
ESPA 4.4.4: Used when fire alarm information shall be transmitted to and presented in a paging system.
EBLTalk: Used when fire alarm information shall be transmitted to and presented in a separate PC system,
via RS232 or via TCP/IP. EBL Talk is an open protocol. For more information see "EBL Talk Protocol"
Technical Description (MEW00532).
SIA: Used when fire alarm information shall be transmitted to and presented in a separate PC system, via
the SIA protocol.
MODBUS: Used when fire information shall be transmitted via MODBUS protocol. Only occurrence of fire
alarm per zone is registered.
MODBUS V2: Used when fire information shall be transmitted via MODBUS protocol via TCP/IP. Status
information per alarm-point is registered.
COM PORT SETTINGS
COM port settings are used for the serial communication (RS232) setup used with EBLTalk or ESPA 4.4.4
protocols.
Normally defaults settings are used for EBLTalk or ESPA 4.4.4, but it's possible to change to suitable
settings depending on corresponding client communication settings.
Press the Reset defaults button to restore the defaults settings for COM port.
EBLTALK SETTINGS
EBLTalk can be used via COM-port (RS232) or via Ethernet TCP/IP port
SIA SETTINGS
Client IP (MAS) address and Sender ID are required. (Provided via the Local Area Network (LAN)
administrator and/or SIA administrator.)
ESPA 4.4.4 SETTINGS
ESPA 4.4.4 uses a COM-port and need a ESPA file to be defined. A ESPA file has to either be created
(Create) or an existing file has be selected (Browse).
MODBUS SETTINGS
MODBUS uses a COM-port and only 8 bits data with 1 stopbit is supported. A slave ID needs to be defined
which is used by a Modbus software to retrieve data.
MODBUS V2 SETTINGS
MODBUS V2 uses default TCP/IP port 502. A slave ID needs to be defined which is used by a Modbus
software to retrieve data.
EBLNET SETTINGS
EBLnet is used to connect the EBL system to a Security Management system.
EBLnet license 5097 is a kit containing:
• EBLnet license number document
16
TECHNICAL DESCRIPTION 1598 • DOCUMENT NUMBER: MEW01930 • REVISION: 4

Advertisement

loading
Need help?

Need help?

Do you have a question about the WEB-SERVER II and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Fp-web2