4. POWER SUPPLY
4. POWER SUPPLY
24 V DC (Molex 3.5) connector. Two power cables are supplied.
The EBL512 cable (3 m) has a plug-in connector for the Web-server II and shall be connected to a 24 V
power supply (to the EBL512 c.i.e. or an external power supply) as follows:
Brown: +24 V DC;
Black: 0 V (GND);
Blue: Function earth (must be connected to Frame Ground).
The EBL512 G3 and EBL128 cable (0.65 m) has two plug-in connectors. One is for the Web-server II and
the other can be directly connected to "J4" at the EBL128 c.i.e board. For system EBL512 G3, the following
is valid: One is for the Web-server II and the other cable connector has to be removed. The wires shall then
be connected to the following screw terminals on the main board:
Brown to "J3:1" (+24 V DC),
Blue to "J3:2" (0 V) and
Green to "J2:3" (Earth).
5. SOFTWARE
Depending on the downloaded software, the web-server II can be used for WebG3, Web128, EBLWeb, or
OPC512 G3.
5.1. EBLWEB
This hardware and software combination is a web-server.
EBLWeb is the software for EBL512 G3 (version ≥ 2.0) or EBL128 (version ≥ 2.0)
The Web-server II with the EBLWeb software is used when one EBL512 G3 / c.i.e. or an EBL512 G3
system with two or more c.i.e. shall be connected to Internet / an intranet (LAN), to a Security Management
system and/or as a Gateway as follows:
• For presentation of the actual EBL512 G3 status in a PC (web browser).
• For remote control of the EBL system (via encrypted and safe two-way communication).
• As an e-mail client.
• EBLnet (via TCP/IP), for connection of an EBL system to a Security Management system.
• As a Gateway.
TECHNICAL DESCRIPTION 1598 • DOCUMENT NUMBER: MEW01930 • REVISION: 4
9
Need help?
Do you have a question about the WEB-SERVER II and is the answer not in the manual?
Questions and answers