11. REMOTE OPERATIONS
INTERLOCKING OUTPUT
All outputs of type "interlocking" can be collectively disabled / re-enabled (all at the same time) in all control
units or in a specified c.i.e. (00-29).

11.1.5. ALARM DEVICES

All outputs of type "alarm devices" can be collectively disabled / re-enabled (all at the same time) in all c.i.e.

11.1.6. ROUTING EQUIPMENT

A submenu with Fire routing equipment and Fault routing equipment.
FIRE ROUTING EQUIPMENT
The FIRE output for routing equipment (fire brigade tx) can be disabled / re-enabled.
FAULT ROUTING EQUIPMENT
The FAULT output for routing equipment (fault tx) can be disabled / re-enabled.

11.1.7. ALERT ANNUNCIATION

The Alert Annunciation function can be disabled / re-enabled.
NOTE! This operation has higher priority than any time channel controlling this function.

11.1.8. COM-LOOP / ZONE LINE INPUT

A sub menu with the three types that can be disabled.
COM-LOOP
A specified COM Loop (0-3) in a specified c.i.e. (00-29) can be disabled / re-enabled.
ZONE-LINE INPUT
A specified zone line input (0-7) on a specified 8 zones expansion Board (0-5), in a specified c.i.e. (00-29),
can be disabled / re-enabled.
ZONE INTERFACE
The zone line input (0) on a specified COM loop unit (3361) / technical number (Tech. No.), can be disabled
/ re-enabled.
NOTE! In system EBL128 the tech.no. is "000" plus the COM loop address, for example 000123.
45
TECHNICAL DESCRIPTION 1598 • DOCUMENT NUMBER: MEW01930 • REVISION: 4