Download Print this page

Event Log; All Log; Alarm Log; Interlocking Log - Panasonic WEB-SERVER II Technical Description

Hide thumbs Also See for WEB-SERVER II:

Advertisement

10. EBLWEB

10.5. EVENT LOG

Press the Event log button to show the Event log view.
The event log of EBLWeb consists of five types of logs, where three of them are the same as in the control
unit, namely, Alarm log, Interlocking log and General event log. All logs in EBLWeb are circular logs. The
events in an EBL-system are stored in both the EBL512G3/EBL128 c.i.e. and in the web-server.
If the web-server is disconnected, the events during that time will not be saved in the web-server, not shown
in the event log. When you restart the web-server, the event log will be erased.
The Time (date & time), and Event (event text) is displayed.
Description = Additional information of the event when applicable.
User = The user that performed that specific event.
Origin = The source where the event originated from.

10.5.1. ALL LOG

The all log is a special log in EBLWeb that collect all events in the same log with a capacity of 9999 log
events.

10.5.2. ALARM LOG

This log contains all alarm related events. This log shall show the same events as the CU alarm log with a
capacity of 999 log events
.

10.5.3. INTERLOCKING LOG

This log contains all interlocking related events. This log shall show the same events as the CU interlocking
log with a capacity of 999 log events.

10.5.4. GENERAL LOG

This log contains all general events. This log shall show the same events as the CU general log with a
capacity of 999 log events.

10.5.5. WEB LOG

This log contains all web related events, with a capacity of 999 log events.

10.5.6. TEST MODE ALARM

This is a log to keep track of the test mode alarms. The test mode alarms normally go back to normal after
10 seconds. This test mode alarm log is used to record the test mode alarms in a list. In this, there's a sub-
menu to send this list of test mode alarms to a pre-defined e-mail recipient and also clear the list from all
recorded test mode alarms.
38
TECHNICAL DESCRIPTION 1598 • DOCUMENT NUMBER: MEW01930 • REVISION: 4

Advertisement

loading
Need help?

Need help?

Do you have a question about the WEB-SERVER II and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Fp-web2