BASIC FACTORY CONFIGURATION - OPERATING PROFILES (MODE)
PARAMETER
Temperature
Relative humidity - RH
Air quality - CO2 content
Supply capacity
Exhaust capacity
•
Work profiles: Comfort, Optimum, Economic require the time and date of their validity to be set in the calendar.
•
Standby operating profile - requires parameter setting:
o
StandBy time, i.e. the minimum time for which the AHU is awakened in StandBy mode,
o
Wake-up time, i.e. the time determining the interval between automatic wake-ups of the AHU
in standby mode.
•
* - humidity control requires the unit to be equipped with humidification and dehumidification functions,
otherwise the values are read-only,
•
** - 100% means the performance from the selection sheet.
•
X – control is user configurable. The minimum air flow must be observed.
AHU
VVS021c
VVS030c
VVS040c
VVS055c
VVS075c
www.vtsgroup.com
°C
T
RH*
%
ppm
ppm
3
V *
% m
/h
S
3
V *
% m
/h
E
OIMM VENTUS COMPACT HP - ver.5.0.9 (10.2024)
WORK PROFILES
Comfort**
Optimum
Comfort**
Low
22
22
50
50
600
600
100
X
100
X
MINIMUM AIR FLOW
3
[m
/h]
1470
1470
2800
2800
5250
Economic
StandBy
Ekono
StandBy
22
22
50
50
900
900
X
X
X
X
68