7.10 GSM COMMUNICATION
The device is equipped with automatic remote identification, configuration and data exchange
mechanisms with external manufacturer systems as standard. A GSM gateway is installed inside the
device. The GSM gateway is equipped with a SIM card if the device installation has been declared in EU
countries.
!
!
The GSM gateway is connected by default (RJ45) to the address 92.168.1.111/24
!
After entering the address: 192.168.1.111 or 192.168.1.111:80, the visualization from the Carel
controller is displayed (just like after connecting to the controller).
!
After entering the address 192.168.1.111:8080 (http) or 192.168.1.111:8443 (https), the service
interface appears (by default Login: admin, Password: admin).
!
In the gateway interface, you can:
change the network parameters of the port through which you connect (the user is only
interested in the port on the housing, the gateway is responsible for forwarding the connection
to the controller),
connect to WIFI,
change the access password to the interface,
change the PIN code for the SIM card.
7.11 MODBUS RTU RS485 COMMUNICATION
www.vtsgroup.com
OIMM VENTUS COMPACT HP - ver.5.0.9 (10.2024)
59

Advertisement

loading
Need help?

Need help?

Do you have a question about the VENTUS COMPACT HP VVS021c and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Ventus compact hp vvs075cVetus compact hp vvs021cVetus compact hp vvs030cVetus compact hp vvs040cVetus compact hp vvs055cVetus compact hp vvs075c