8 Operation
8.8.2

Configuring active and reactive power setpoints

Supported inverters for the limitation of the active power feed-in to 0%
The limitation of the active power feed-in to 0% are only supported by inverters that support
the fallback function. In the event of a communication failure between the product and the
inverter, the inverter is reduced to an output power of 0% during fallback). For more
information see the inverter manual at www.SMA-Solar.com.
Requirements:
☐ The configuration for the active power limitation must be agreed upon with the responsible
grid operator.
☐ There must be an appropriate energy meter installed at the grid-connection point within the
system.
☐ The user interface must be open and you must be logged in as Installer or Administrator.
Procedure:
1. Select the system in the focus navigation.
2. Select the menu item Grid management service in the menu Configuration.
3. Select the button Configuration & activation in the Active and reactive power row.
☑ The installation assistant will open.
4. Make the settings for Grid settings, Active power and Reactive power according to the
specifications required by the grid operator and laid down in the standards and confirm each
with [Next].
5. Click on [Save].
8.8.3
Configure additional specifications from the grid operator
for the country data set.
During device registration, the required country data sets are selected for the detected devices. To
achieve the correct control speed for the country data set, you need to make additional settings.
Requirements:
☐ The user interface must be open and you must be logged in as Installer or Administrator.
Procedure:
1. Select the system in the focus navigation.
2. Select the menu item Grid management service in the menu Configuration.
3. Select the button Configuration & activation in the Active and reactive power row.
4. Open the configuration wizard for Grid operator specifications under Active power.
5. In case of a manual setpoint, activate Manual setpoint for active power limitation and
enter the active power limitation specified by the grid operator.
64