SMA Solar Technology AG
The following connection options ar available:
• Establishing a direct Wi-Fi connection by entering the Wi-Fi data from the type label
• Establishing a direct Wi-Fi connection by scanning the QR code from the device label
7.4.2.2 Access information for direct Wi-Fi connection
Communication disturbances in the local network
The IP address range 192.168.12.0 to 192.168.12.255 is occupied for communication
amongst SMA products and for direct access to SMA products.
Communication problems might occur if this IP address range is used in the local network.
• Do not use the IP address range 192.168.12.0 to 192.168.12.255 in the local network.
Access information for the direct WiFi connection can be found below:
• SSID: SMA[serial number] (e.g., SMA0123456789)
• Device-specific Wi-Fi password: WPA2-PSK (see type label of the product)
• Default access address: https://192.168.12.3
7.4.2.3 Establishing a direct Wi-Fi connection by entering the Wi-Fi data
Requirements:
☐ A smart terminal (e.g. laptop) must be available.
Procedure:
1. Activate the Wi-Fi access point on the product. Tap on the enclosure lid of the product twice.
☑ The COM LED is intermittently flashing orange and green for approx. 5 seconds. The Wi-
Fi access point is then activated for approx. 30 minutes. Once this period has expired,
the Wi-Fi access point is deactivated automatically.
2. Search for Wi-Fi networks with your smart device.
3. Select the SSID of the product SMA[serial number] in the list with the detected Wi-Fi
networks.
4. Enter the device-specific Wi-Fi password (see WPA2-PSK on the type label).
5. Open the web browser of your smart terminal and enter the IP address https://
192.168.12.3 into the address bar or, if your smart terminal supports MSDNs services,
SMA[serialnumber].local or https://SMA[serialnumber].
☑ When you connect to the user interface for the first time, the welcome page opens. The
Commissioning Assistant for configuring the product can be started via the welcome
page.
☑ The login page of the user interface opens if the product has already been configured.
7.4.2.4 Establishing a direct Wi-Fi connection by scanning the QR code
Requirements:
☐ A smart terminal (e.g. laptop) must be available.
Operating manual
7 Commissioning
EDMM-20-BE-en-10