SMC Networks PF3W3 Series Operation Manual page 49

Digital flow switch (remote type monitor unit)

Advertisement

OFF
ON
Use the
and
buttons to enter the flow value that will
generate full span analogue output (5 V or 20 mA). The
Sub screen
entered flow value can be in the range: 10% of maximum
rated flow, to the upper display limit.
Press the
button to confirm.
Return to the function selection mode.
[F22] Setting of analogue output is completed.
∗: The analogue output of the remote sensor is saturated at approx. 5.6 V, so use it with 110% or lower of maximum rated flow.
Turn the power off and turn it on again if the setting of analogue output is changed.
-49-
No.PF※※-OMN0012-I