No. Parameter
Name
59
Activation Time for Electronic
Thermal Protection Function
60
Over-torque
Detection
61
62
63
Reserved
64
User Defined
Parameter
Displayed
65
Coefficient K
Function
Explanation
Over-torque
detection mode
Over-torque
detection level
Over-torque
detection time
Displays user
defined parameter
on digital keypad/
display
Coefficient for line
speed
select
73
VLT
Parameter
Value
30 - 300 sec
00:Over-torque detection not
enabled
01:Over-torque detection during
constant speed operation.
Drive operation halted after
over-torque (OL2).
02:Over-torque detection during
constant speed operation.
Operation continues after
over-torque detection (OL2).
03:Over-torque detection during
operation.
Operation continues after
over-torque detection (OL2).
04:Over-torque detection during
operation.
Drive operation halted after
over-torque (OL2).
30 - 200%
0.0 - 10.0 sec
00:Displays the drive output
frequency (Hz)
01:Display user-define outpu Freq
02:Display Output Voltage (E)
03:Display DC Bus Voltage (u_)
04:Display PV (i)
05:Display the counter value (c)
06:Display the program freq. (F)
07:Display the par. setting (Pr.00)
08:Reserved
09:Displays Output current (A)
10:Displays Fwd/Rev mode
0.01 - 160.0
® ® ® ® ®
MICRO
Factory
Setting
60
00
150
0.1
06
1.00