Pr.64 User Defined Function for Display
Factory Setting 06
Units None
Settings
00 Displays AC drive output frequency (Hz)
01 Displays the user-defined output frequency H*P65
02 Displays the Output Voltage (E)
03 Displays the DC Bus Voltage (u_)
04 Displays the PV (i)
05 Displays the value of the internal counter (c)
06 Displays the setting Frequency (F or o=%)
07 Displays the parameter setting (Pr.00)
08 Reserved
09 Displays the Output Current (A)
10 Displays program operation (0.xxx), Frd, or Rev
The parameter can be set to display the user-defined value. (where V = H x Pr.65)
Pr.65 Coefficient of Line Speed
Factory Setting 1.00
Units 0.01
Parameter value 0.01 - 160.0
Coefficient K determines the multiplying factor for the user-defined value (v). The value
of the user-defined setting (v) is calculated and displayed as follows: Display Value, v =
output frequency x K. The maximum value that can be displayed is 999. If the value of
"v" exceeds "999" the display value defaults to v = output frquency x 0.1.
Pr.66 Communication Frequency
Factory Setting 0.00
Units 0.1
Parameter value 0.00 - 400.0 Hz
Pr.67, Pr.68, Pr.69 Frequency Setting Prohibited
Pr.67, 68, 69 Skip Frequency 1, 2, 3
Factory Setting 0.00 Hz
Units 0.01 Hz
Parameter value 0.00 - 400.0 Hz
This parameter determines the three skip frequencies which in conjunction with Pr.70,
Skip Frequency Band, will cause the AC motor drives to skip operation at each
frequency band. Note: Pr.67 > Pr.68 > Pr.69.
55
® ® ® ® ®
VLT
MICRO
Need help?
Do you have a question about the VLT MICRO and is the answer not in the manual?
Questions and answers
hola, tengo un inversor de hercios 176F7330 de la marca danfoss y se le daño una resistencia, esta exploto y no puedo ver su valor lo que me impide cambiarla, lo que quiero preguntar es si es posible que me ayuden dando algun diagrama o información en el cual indique cual es el valor de la resistencia en homs y cuantos de cuantos wats debe ser