Pr.36, Pr.37 – Reference Frequency: Upper / Lower limit
Pr.36 Reference Frequency Upper Limit
Factory Setting 400.0 Hz
Units 0.01 Hz
Parameter Value 0.01 - 400.0 Hz
This parameter programs the upper limit of the reference frequency in 0.01 Hz increments.
Pr.37 Reference Frequency Lower Limit
Factory Setting 0.00 Hz
Units 0.01 Hz
Parameter Value 0.10 - 400.0 Hz
Determines the lower limit of the reference frequency in 0.01 Hz increments.
Output frequency
Application Notes:
1. Parameters 36, 37 are provided to prevent damage to the AC motor and
applicable machinery. Under certain conditions a motor can overheat and/or machinery
can be damaged at excessively high speeds.
2. The lower limit for AC drive operation is determined by the greater value of Pr.08
(Minimum Output Frequency) and Pr.37 (Reference Frequency Lower Limit). The
upper limit for AC drive operation is determined by the lesser value of Pr.03
(Maximum Output Frequency and Pr.36 Reference Frequency Upper Limit).
Pr.38 Multi-Function Input Terminals (M0, M1)
Factory Setting 00
Units None
Settings 00 - 02
Pr.39 Multi-Function Input Terminals (M2)
Factory Setting 05
Units None
Settings 03 - 20
Pr.36
Pr.37
37
® ® ® ® ®
VLT
Input frequency
Value M0,M1 Function
00
M0: Fwd./Stop, M1: Rev./Stop1
01
M0: Run/Stop, M1: Fwd./Rev.1
02
3-Wire Operation Control Mode1
MICRO
Need help?
Do you have a question about the VLT MICRO and is the answer not in the manual?
Questions and answers
hola, tengo un inversor de hercios 176F7330 de la marca danfoss y se le daño una resistencia, esta exploto y no puedo ver su valor lo que me impide cambiarla, lo que quiero preguntar es si es posible que me ayuden dando algun diagrama o información en el cual indique cual es el valor de la resistencia en homs y cuantos de cuantos wats debe ser