Danfoss VLT MICRO Manual page 7

Adjustable frequency drive
Hide thumbs Also See for VLT MICRO:
Table of Contents

Advertisement

Relay outputs:
No. of programmable relay outputs ........................................................................... 1
Terminal numbers ............................................... RA, RC (N.O.) RB, RC (N.C.) (Form C)
Max. terminal load rating ............................................................ 120 VAC/28 VDC, 5 A
........................................................................................................... 240 VAC, 2.5 A
Brake resistor terminals:
Terminal numbers ............................................................................................. B1, B2
Cable lengths and cross-sections:
Use 75° grade copper wire minimum
Max. motor cable length ...................................................................................... 50 m
Max. cable cross-section for line, motor and brake .......................... 14 AWG (2.0 mm
Max. cable cross-section for control terminals ................................. 14 AWG (2.0 mm
Control characteristics:
Frequency range ..................................................................................... 0.1 - 400 Hz
Resolution on output frequency ..................................................................... ±0.1 Hz
Speed, control range (open loop) ........................................... 1:20 of synchro. speed
Speed, accuracy (open loop) ........................................... < 1800 rpm: max. error 2%
....................................................... > 1800 rpm: max. error of 0.5% of actual speed
Environment:
Enclosure .............................................................................. Protected chassis (IP20)
Vibration test ..................................................... 1.0 g less than 20Hz, 0.6 g 20-50Hz
Max. relative humidity .............................................. less than 90% (non-condensing)
Ambient temperature .......................................................................... –10°C - +50°C
Temperature during storage/transport ..................................................... –20 - +60°C
Max. altitude above sea level ........................................................... 3300 ft. (1000 m)
7
® ® ® ® ®
VLT
MICRO
2
2
)
)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT MICRO and is the answer not in the manual?

Questions and answers

juan
January 20, 2025

hola, tengo un inversor de hercios 176F7330 de la marca danfoss y se le daño una resistencia, esta exploto y no puedo ver su valor lo que me impide cambiarla, lo que quiero preguntar es si es posible que me ayuden dando algun diagrama o información en el cual indique cual es el valor de la resistencia en homs y cuantos de cuantos wats debe ser

User image 678dad90131ca

Table of Contents

Save PDF