NE1A-series Controller Operating Modes

10-1 NE1A-series Controller Operating Modes

10-1-1 Operating Mode Overview

SELF-DIAGNOSTIC Mode
CONFIGURING Mode
IDLE Mode
RUN Mode
ABORT State
CRITICAL ERROR State
210
The following modes are supported by the NE1A-series Controller.
The NE1A-series Controller performs self-diagnosis internally. This is
required to ensure safety functions.
CONFIGURING Mode exists while waiting for the completion of configuration
from the Network Configurator. The NE1A-series Controller switches to Con-
figurating Mode when it is not yet configured after initialization has been com-
pleted or when there is an error in the configuration data.
IDLE Mode exists while waiting for RUN Mode after initialization has been
completed.
Non-safety-related control (standard I/O communications, message communi-
cations, etc.) is supported.
Safety control (user program, safety I/O communications, safety I/O refresh
control) and non-safety-related control (standard I/O communications, mes-
sage communications, etc.) are both supported.
The NE1A-series Controller switches to Abort Mode if the Controller's switch
setting is changed after the configuration has been completed. The Controller
stops all functions except for message communications and puts them in the
safety state.
When Controller's switch settings must be changed due to user system
changes, reset the Controller to the default settings. Refer to SECTION 9
Other Functions for the reset function.
The NE1A-series Controller switches to this state if a critical error occurs.
The Controller stops all functions and puts them in the safety state.