Receiving Explicit Messages
Error Code (Response)
The following error codes defined in DeviceNet may be returned.
Response
Error name
code
08FF
Service not
supported
13FF
Not enough data
15FF
Too much data
16FF
Object does not
exist
20FF
Invalid parameter The specified operation command data is not supported.
Error in the service code.
The data is shorter than the specified size.
The data is longer than the specified size.
The specified class ID or instance ID is not supported.
Section 6-1
Cause
111