Omron NE1A-SCPU01 - 07-2009 Operation Manual page 317

Safety network controller
Hide thumbs Also See for NE1A-SCPU01 - 07-2009:
Table of Contents

Advertisement

A-3-2
Explicit Messages: NE1A-SCPU02/NE1A-SCPU02-EIP
Reading General Status
Explicit
Service
message
Read Unit General
Read
Status
Reading I/O Area
Explicit
Service
message
Read I/O Area
Read
Function
Service
Reads the Unit's general
0E hex
status.
Function
Service
Reads the Unit's I/O data.
4B hex
Instance ID Specification
Range:
Local input = 01
Local output/test output = 02
Safety input = 05
Safety output = 06
Address Specification Range:
Local input: 0 to 4
Local output/test output: 0 or 1
Safety input: 0 to 511
Safety output: 0 to 511
Command
Class
In-
At-
code
stance
tribute
ID
ID
ID
39 hex 01 hex
6E hex
Command
Class
In-
At-
code
stance
tribute
ID
ID
ID
306
01, 02,
---
hex
05, and
06 hex
Appendix A
Response
Data size
---
1 byte
Response
Data size
First and second
Read data
byte offset
address:
0000 to 01FF
hex (0 to 511),
Third and fourth
byte read size:
0001 to 0100
hex (1 to 48)
283