Safety Slave Function
Note
Setting Local I/O Monitor Data
Note
Serious injury may possibly occur due to loss of required safety functions. The
necessary measures for safety data are not taken for data with the non-safety
data attribute from NE1A-series Controller's internal status information allocated
to the Safety Master. Therefore, do not use this data to configure the Safety Con-
trol System.
Controllers with Unit Version 1.0 or Later, Including Controllers that Sup-
port EtherNet/IP
Tag name
General Status
Local Input Status 1 to N (See
note.)
Local Output Status
Test Output/Muting Lamp Sta-
tus 1 to M (See note.)
For the NE1A-SCPU01-V1(-EIP), N = 2 and M = 1. For the NE1A-SCPU02(-
EIP), N = 5 and M = 2. The sizes of the local input status and test output/mut-
ing lamp status data can be specified in bytes.
If the I/O type of the Safety Slave I/O is set to Slave IN for a NE1A-series Con-
troller with unit version 1.0 or later (including Controllers that support Ether-
Net/IP), the following local I/O monitor information can be added to the
transmission data after the status information. Refer to 4-3-3 Remote I/O Area
Data Configuration for details on the local I/O monitor information.
Local I/O Monitor
Local Input Monitor 1 to N (See note.)
Local Output Monitor
For the NE1A-SCPU01-V1(-EIP), N = 2. For the NE1A-SCPU02(-EIP), N = 5.
The size of the local input monitor data can be specified in bytes.
!WARNING
Data size
Byte
Non-safety
Byte
Safety
Byte
Safety
Byte
Non-safety
Data size
Byte
Safety
Byte
Non-safety
Section 4-5
Attribute
Attribute
91