Omron NE1A-SCPU01 - 07-2009 Operation Manual page 50

Safety network controller
Hide thumbs Also See for NE1A-SCPU01 - 07-2009:
Table of Contents

Advertisement

System Configuration
Connecting via an EtherNet/IP-DeviceNet Router
NE1A Safety Network Controllers can be accessed through the
EtherNet/IP-DeviceNet Router from a Network Configurator at
any of the following locations.
1) Connected via to a USB port on a Safety Network Controller
on a different DeviceNet Safety network
2) Connected to an EtherNet/IP network
3) Connected to a different DeviceNet Safety network
ED Router
(NE1A-EDR01)
Note
Direct Connection to EtherNet/IP (for Controllers that Support EtherNet/IP)
Remote configuration and monitoring are enabled for standard
and safety devices on both EtherNet/IP and DeviceNet
networks, using the Network Configurator.
16
If the networks are built using an NE1A-EDR0 EtherNet/IP-DeviceNet Router,
a Network Configurator connected at any point can be used to access the
NE1A Safety Network Controllers through the EtherNet/IP-DeviceNet Router.
The Network Configurator can be at any of the following locations.
• Connected via to a USB port on a Safety Network Controller on a different
DeviceNet Safety network (See note 1.)
• Connected to an EtherNet/IP network
• Connected to a different DeviceNet Safety network
Ethernet (EtherNet/IP)
1) Network Configurator
USB
DeviceNet Safety
DeviceNet Safety
DST1-series Slaves
(1) The NE1A-SCPU01-V1 with unit version 2.0 or later (including Control-
lers that support EtherNet/IP) or NE1A-SCPU02 with unit version 2.0 or
later (including Controllers that support EtherNet/IP) is required. NE1A
Safety Network Controllers cannot be accessed through a EtherNet/IP-
DeviceNet Router from a Network Configurator connected to the USB
port on the NE1A-SCPU01-V1 with unit version 1.0, or the NE1A-
SCPU02 with unit version 1.0 or earlier.
(2) Refer to the EtherNet/IP-DeviceNet Router Operation Manual (Cat. No.
Z912) for details on the NE1A-EDR01 EtherNet/IP-DeviceNet Router.
Remote configuration and monitoring are enabled for standard and safety
devices on both EtherNet/IP and DeviceNet networks.
Network Configurator
EtherNet/IP
NE1A-series Controller
(supporting EtherNet/IP)
DeviceNet
2) Network Configurator
NE1A Safety
Network Controller
DeviceNet Safety
Section 1-2
3) Network Configurator
DeviceNet Safety
DST1-series Slaves
NE1A-series Controller
(supporting EtherNet/IP)
DeviceNet Safety
DST1-series
DeviceNet Safety Slaves

Hide quick links: