Using the Simple Program Function

tr-t
sp
Initial Setting Level
Transfer Output
C
tr-h
Upper Limit
1300
C
tr-h
200
Initial Setting Level
Transfer Output
C
tr-l
Lower Limit
-200
C
tr-l
-50
Operation Level
PV/SP
C
25
100

4-15 Using the Simple Program Function

4-15-1 Simple Program Function

3. Press the U Key to select sp (set point).
4. Select the Transfer Output Upper Limit parameter by pressing the M Key.
5. Use the D Key to set the parameter to 200. The default is 1300.
6. Select the Transfer Output Lower Limit parameter by pressing the M Key.
7. Use the U Key to set the parameter to 50. The default is 200.
8. To return to the operation level, press the O Key for at least one second.
• The simple program function can be used for the following type of control.
SP
Set point
PV
RSET
STRT
Section 4-15
Soak time
END display
END output
Select either
STOP or RUN.
Wait band
Wait band
129