Using The Extraction Of Square Root Parameter; Mv At Pv Error - Omron E5AN User Manual

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Using the Extraction of Square Root Parameter

4-16-3 MV at PV Error

Note
MV upper limit
Manipulated variable
PID
calculations
MV lower limit
Note

4-17 Using the Extraction of Square Root Parameter

Extraction of Square
Roots
Extraction of Square Root Enable
sqr
off
Extraction of Square Root Low-cut
Point
sqrp
0.0
• The MV to be output for input errors can be set.
The MV at stop takes priority when stopped and the manual MV takes pri-
ority in manual mode.
Parameter name
MV at PV ERROR
5.0 to 105.0 for standard
control
105.0 to 105.0 (heating/cool-
ing control)
The order of priority is as follows: Manual MV > MV at stop > MV at PV error.
• The order of priority of the MVs is illustrated in the following diagram.
MV at PV Error
Input error
Time
When the Manual MV Limit Enable parameter is set to ON, the setting range
will be the MV lower limit to the MV upper limit.
• For analog inputs, the Extraction of Square Root parameter is provided
for inputs so that differential pressure-type flow meter signals can be
directly input.
• The default setting for the Extraction of Square Root parameter is OFF.
The Extraction of Square Root Enable parameter must be set to ON in
order to use this function.
• If the PV input (i.e., the input before extracting the square root) is higher
than 0.0% and lower than the low cut point set in the Extraction of
Square Root Low-Cut Point parameter, the results of extracting the
square root will be 0.0%. If the PV input is lower than 0.0% or higher
than 100.0%, extraction of the square root will not be executed, so the
result will be equal to the PV input. The low-cut point is set as normal-
ized data for each input, with 0.0 as the lower limit and 100.0 as the
upper limit for the input setting range.
Setting range
%
Manual MV
(See note.)
RUN/STOP
Auto/manual switch
MV at Stop
Section 4-17
Unit
Default
0.0
Output
137

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cnE5enE5gn

Table of Contents