Omron E5AN User Manual page 242

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Initial Setting Level
cp
Control Period (Heating)
c-cp
Control Period (Cooling)
Function
Setting
See
See
orev
Direct/Reverse Operation
Function
Setting
206
• These parameters set the output periods. Set the control periods taking
the control characteristics and the electrical durability of the relay into
consideration.
• For standard control, use the Control Period (Heating) parameter. The
Control Period (Cooling) parameter cannot be used.
• When the heating control output is a current output, the Control Period
(Heating) parameter cannot be used.
• For heating/cooling control, the control period can be set independently
for heating and cooling. The Control Period (Heating) parameter is used
for the heating control output, and the Control Period (Cooling) parameter
is used for the cooling control output
Parameter name
Control Period (Heating)
Control Period (Cooling)
■ Related Parameters
PID ON/OFF (initial setting level): Page 204
• "Direct operation" refers to control where the manipulated variable is
increased when the process value increases. Alternatively, "reverse oper-
ation" refers to control where the manipulated variable is increased when
the process value decreases.
Setting range
or-r: Reverse operation, or-d: Direct operation
The cooling control output and heat-
ing control output must be assigned
to relay or voltage outputs (for driving
SSR).
The control must be set to 2-PID
control.
For the Control Period (Cooling)
parameter, the control must be set to
heating/cooling control.
Setting range
Unit
0.5 or 1 to 99
Second
0.5 or 1 to 99
Second
Section 5-7
Default
20
20
Default
or-r