Calculating Detection Current Values - Omron E5AN User Manual

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms

3-10-3 Calculating Detection Current Values

Heater Burnout Detection 1/2 set value = Normal current value + Burnout current value
Heater overcurrent 1/2 set value = Normal current value + Overcurrent value
AC line
Product
To CT input
AC line
Product
To CT input
2. Star connecting lines: Refer to the following diagram for CT installation po-
sitions.
Note Heater voltage fluctuations are not considered here, so be take that
into account when setting the detection current.
AC line
Product
To CT input
Product
To CT input
3. V connecting lines: Refer to the following diagram for CT installation posi-
tions.
Note Heater voltage fluctuations are not considered here, so be take that
into account when setting the detection current.
Product
To CT input
AC line
Product
To CT input
• Calculate the set value using the following equation:
HS Alarm 1/2 set value = Leakage current value (output OFF) + HS current value
• To set the current for heater burnout when two or more heaters are con-
nected through the CT, use the value from when the heater with the small-
est current burns out. If all of the heaters have the same current, use the
value from when any one of them burns out.
Load (such as a heater)
Load
CT
Load (such as a heater)
CT
CT
CT
Load (such as a heater)
CT
2
Section 3-10
2
2
75