Omron E5AN User Manual page 325

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Adjustment Level
Parameters
Characters
l.adj
Adjustment Level
Display
at
AT Execute/Cancel
cmwt
Communications
Writing
ct1
Heater Current 1
Value Monitor
hb1
Heater Burnout
Detection 1
oc1
Heater Overcurrent
Detection 1
ct2
Heater Current 2
Value Monitor
hb2
Heater Burnout
Detection 2
oc2
Heater Overcurrent
Detection 2
lcr1
Leakage Current 1
Monitor
hs1
HS Alarm 1
lcr2
Leakage Current 2
Monitor
hs2
HS Alarm 2
sp-0
SP 0
sp-1
SP 1
sp-2
SP 2
sp-3
SP 3
ins
Temperature Input
Shift
insh
Upper Limit Temper-
ature Input Shift
Value
insl
Lower Limit Temper-
ature Input Shift
Value
p
Proportional Band
i
Integral Time
d
Derivative Time
c-sc
Cooling Coefficient
c-db
Dead Band
Setting (monitor) value
OFF, AT Cancel
AT-2: 100%AT Execute
AT-1: 40%AT Execute
OFF, ON
0.0 to 55.0
0.0 to 50.0
0.0 to 50.0
0.0 to 55.0
0.0 to 50.0
0.0 to 50.0
0.0 to 55.0
0.0 to 50.0
0.0 to 55.0
0.0 to 50.0
SP lower limit to SP upper
limit
SP lower limit to SP upper
limit
SP lower limit to SP upper
limit
SP lower limit to SP upper
limit
199.9 to 999.9
199.9 to 999.9
199.9 to 999.9
Universal input: 0.1 to 999.9
Analog input: 0.1 to 999.9
0 to 3,999
RT OFF: 0 to 3,999
RT ON: 0.0 to 999.9
0.01 to 99.99
Universal input: 199.9 to
999.9
Analog input: 19.99 to 99.99
Display
Default
off,
OFF
at-2,
at-1
off, on
OFF
0.0
50.0
0.0
50.0
50.0
50.0
0
0
0
0
0.0
0.0
0.0
8.0
10.0
233
40
40.0
1.00
0.0
0.00
Appendix
Unit
Set value
None
None
A
A
A
A
A
A
A
A
A
A
EU
EU
EU
EU
C or F
C or F
C or F
C or F
(See note
1.)
%FS
Second
Second
Second
None
C or F
(See note
1.)
%FS
289

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cnE5enE5gn