Omron E5AN User Manual page 258

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Advanced Function Setting Level
Auxiliary Output * Open in Alarm
sb*n
(*: 1 to 3)
Function
Setting
See
See
hbu
HB ON/OFF
Function
Setting
222
• This parameter sets the output status of auxiliary outputs 1 to 3.
• When Close in Alarm is set, the status of the auxiliary output function is
output unchanged. When Open in Alarm is set, the status of the auxiliary
output function is reversed before being output. The following table shows
the relationship between the auxiliary output function, auxiliary output,
and operation displays (SUB1 to SUB3).
Auxiliary output
Close in Alarm
ON
OFF
Open in Alarm
ON
OFF
Setting range
n-o: Close in alarm, n-c: Open in alarm
■ Related Parameters
Auxiliary output 1 to 3 assignment (advanced function setting level): Pages
240 to 242
• Set to use the heater burnout alarm.
Setting range
on: Enabled, off: Disabled
Auxiliary output 1, 2, or 3 must be
assigned.
Auxiliary output Operation display
function
ON
OFF
OFF
ON
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
Section 5-8
(SUB1 to SUB3)
Lit
Not lit
Lit
Not lit
Default
n-o
Default
on