Omron E5AN User Manual page 169

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Using the Simple Program Function
Operation Level
PV/SP
C
25
100
Initial Setting Level
Input Type
in-t
5
Initial Setting Level
Program Pattern
ptrn
off
ptrn
stop
Operation Level
PV/SP
C
25
100
Adjustment Level
Adjustment Level
l.adj
Display
Adjustment Level
Soak Time
soak
1
soak
10
Set point
PV
RSET
STRT
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Program Pattern parameter by pressing the M Key.
3. Use the U Key to set the parameter to STOP.
4. Press the O Key for at least one second to move from the initial setting
level to the operation level.
5. Press the O Key to move from the operation level to the adjustment level.
6. Select the Soak Time parameter by pressing the M Key.
7. Use the U Key to set the parameter to 10. (The soak time unit is set in
Soak Time Unit parameter in the advanced function setting level. The de-
fault is m (minutes).
Soak time = 10 min
STOP
Section 4-15
Wait band = 3
END display
END output
133