Using the Key Protect Level

4-9

Using the Key Protect Level

4-9-1

Protection

Operation/Adjustment
Protect
oapt
0
Initial Setting/
Communications
Protect
icpt
1
Setting Change
Protect
wtpt
off
110
• To move to the protect level, press the O and M Keys simultaneously for
at least three seconds in operation level or adjustment level. (See note.)
Note The key pressing time can be changed in the Move to Protect Level
Time parameter (advanced function setting level).
• The protect level protects parameters that are not changed during Con-
troller operation until operation is started to prevent them from being mod-
ified unintentionally.
There are four types of protection: operation/adjustment protect, initial
setting/communications protect, setting change protect, and PF Key pro-
tect.
• The protect level settings restrict the range of parameters that can be
used.
The following table shows the relationship between set values and the range
of protection.
Level
Operation
PV
Can be dis-
level
played
PV/SP
Can be dis-
played and
changed
Others Can be dis-
played and
changed
Adjustment level
Can be dis-
played and
changed
• Parameters are not protected when the set value is set to 0.
• The default is 0.
This protect level restricts movement to the initial setting level, communica-
tions setting level, and advanced function setting level.
Set
Initial setting level
value
0
Possible to reach
1
Possible to reach
2
Not possible to reach
• The default is 1.
This protect level restricts key operations.
Set value
OFF
Settings can be changed using key operations.
ON
Settings cannot be changed using key operations. (The protect level
settings, however, can be changed.)
Set value
0
1
Can be dis-
Can be dis-
played
played
Can be dis-
Can be dis-
played and
played and
changed
changed
Can be dis-
Cannot be
played and
displayed and
changed
moving to
other levels is
not possible
Cannot be
Cannot be
displayed and
displayed and
moving to
moving to
other levels is
other levels is
not possible
not possible
Communications
setting level
Possible to reach
Possible to reach
Not possible to reach
Description
Section 4-9
2
3
Can be dis-
played
Can be dis-
played
Cannot be
displayed and
moving to
other levels is
not possible
Cannot be
displayed and
moving to
other levels is
not possible
Advanced function
setting level
Possible to reach
Not possible to reach
Not possible to reach