Initial Setting Level
tr-h
Transfer Output Upper Limit
tr-l
Transfer Output Lower Limit
Function
Transfer output
type
Setting
Set point
Set point during
SP ramp
PV
MV monitor
(heating)
MV monitor
(cooling)
See
See
o1-t
Linear Current Output
Setting
See
See
212
• This parameter sets the upper and lower limit values of transfer outputs.
Setting range
SP lower limit to SP upper limit
SP lower limit to SP upper limit
Temperature Input setting range lower limit
to input setting range upper
limit
Analog
Analog scaling lower limit to
analog scaling upper limit
Standard
5.0 to 105.0
Heating/
0.0 to 105.0
cooling
0.0 to 105.0
■ Related Parameter
Transfer output type (initial setting level): Page 210
This parameter selects the output type for linear current outputs.
Linear current
output
4-20: 4 to 20 mA
0-20: 0 to 20 mA
Note
Even when control output 1 is used as a control output or a simple transfer
output, 0 to 20 mA can be used.
■ Related Parameter
Transfer output type (initial setting level): Page 210
There must be a transfer output or a
current output.
The transfer output type must not be
set to OFF.
Transfer
output lower
limit
SP lower limit
Input setting
range lower
limit
Scaling lower
limit
0.0
Control output 1 must be a current
output.
Default
4-20
Section 5-7
Default
Unit
Transfer
output upper
limit
SP upper limit
EU
Input setting
range upper
limit
Scaling upper
limit
100.0
%