Loop Burnout Alarm
Initial Setting Level
alt1
12
Move to Ad-
amov
vanced Function
Setting Level
0
Advanced Function Setting Level
Parameter
init
Initialization
off
Advanced Function Setting Level
LBA Detection
lba
Time
0
C
lba
10
Advanced Function Setting Level
LBA Level
C
lbal
8.0
C
lbal
8.0
Advanced Function Setting Level
LBA Band
C
lbab
3.0
C
lbab
3.0
Initial Setting Level
Input Type
in-t
5
Operation Level
PV/SP
C
25
100
3. Press the U Key to set the parameter to 12.
4. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key. (For details on moving between levels, refer to 4-8 Moving
to the Advanced Function Setting Level.)
5. Press the D Key to enter the password ( 169), and move from the initial
setting level to the advanced function setting level.
6. Select the LBA Detection Time parameter by pressing the M Key.
7. Press the U Key to set the parameter to 10.
8. Select the LBA Level parameter by pressing the M Key.
9. Press the U Key to set the parameter to 8.0. (The default is 8.0.)
10. Select the LBA Band parameter by pressing the M Key.
11. Press the U or D Key to set the parameter to 3.0. (The default is 3.0.)
12. Press the O Key for at least one second to move from the advanced
function setting level to the initial setting level.
13. Press the O Key for at least one second to move from the initial setting
level to the operation level.
Section 4-12
121