Built-In Inputs - Omron CJ - 09-2009 Operation Manual

Programmable controllers
Table of Contents

Advertisement

PLC Setup

7-1-2-11 Built-in Inputs

High-speed Counter 0 Operation Settings
High-speed Counter 0 Enable/Disable
Programming
Settings
Console
address
Word
Bits
+50
12 to 15 0 hex: Don't Use
Counter.
1 hex*:
Use Counter
(60 kHz).
2 hex*:
Use Counter
(100 kHz).
High-speed Counter 0 Pulse Input Setting (Pulse Input Mode)
Programming
Settings
Console
address
Word
Bits
+50
00 to 03 0 hex: Differential
phase inputs
1 hex: Pulse +
direction inputs
2 hex: Up/Down
inputs
3 hex: Increment
pulse input
316
The following tables show the CX-Programmer's settings. These settings are
for CJ1M CPU Units equipped with the built-in I/O functions.
Note In the CX-Programmer version 3.1 or lower, the Tab Page's name is Built-in
I/O Settings.
Default
0 hex
Specifies whether or not high-speed
counter 0 is being used.
Note When high-speed counter 0 is
Default
0 hex
Specifies the pulse-input method for
high-speed counter 0.
Function
enabled (setting 1 or 2), the
input operation settings for
IN8 and IN9 are disabled. The
input operation setting for IN3
is also disabled if the reset
method is set to Phase-Z sig-
nal + software reset.
Function
Section 7-1
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When power is
turned ON
Related
Time when
Auxiliary
setting is read
Area flags/
by CPU Unit
bits
---
When power is
turned ON