Omron CJ - 09-2009 Operation Manual page 228

Programmable controllers
Table of Contents

Advertisement

Power Supply Units
TEST switch
Alarm output
Self-diagnostic Function
Error name
Display
Unit overheated
error
Unit error
Comparison between the CJ1W-PA205C and CJ1W-PA205R
Item
RUN contact output
Not supported
Terminal block
arrangement
180
0.5 s
0.5 s
0.5 s
Note Under normal application conditions, the replacement notification function will
operate after several years or even tens of years. When using a Power Supply
Unit for an extended period of time, periodically check operation with the
TEST switch as described above and be sure the alarm output functions prop-
erly.
Alarm output
status
OFF
OFF
Note If the error continues for 3 hours or longer, the replacement notification func-
tion will be disabled. Even if the cause of the overheating is removed, the dis-
play will continue as "Hot," and the notification output will remain OFF. In this
state, the internal parts may deteriorate even if the PC operation is normal, so
replace the Power Supply Unit.
CJ1W-PA205C
CJ1W-PA205C
100 to 240 VAC
INPUT
L1
AC input
L2/N
LG
GR
NC
Unconnected
terminals
NC
3 s
ON
0.5 s
0.5 s
ON
Error details (cause)
Internal overheating has
occurred in the Power Supply
Unit as a result of usage under
conditions that exceed the spec-
ified values, insufficient ventila-
tion, or incorrect installation.
(See note.)
System error from external
noise or hardware malfunction.
CJ1W-PA205R (for comparison)
Supported
100 to 240 VAC
INPUT
RUN
OUTPUT
240 VAC
24 VDC
2A RESISTIVE
Section 3-4
0.5 s
OFF
ON
Recovery method
Remove the cause of the over-
heating error.
Turn ON the input's power sup-
ply again. If the Unit does not
recover, the error may be
caused by a Unit malfunction.
Consult with your OMRON rep-
resentative.
CJ1W-PA205R
L1
AC input
L2/N
LG
GR
RUN output
(RUN contact)

Advertisement