Unit Settings Tab Page - Omron CJ - 09-2009 Operation Manual

Programmable controllers
Table of Contents

Advertisement

PLC Setup
7-1-2-5

Unit Settings Tab Page

Basic I/O Unit Input (Rack) Response Times
Item
Console address
Rack 0, Slot 0
+10
Rack 0, Slot 1
Rack 0, Slot 2
+11
Rack 0, Slot 3
Rack 0, Slot 4
+12
Rack 0, Slot 5
Rack 0, Slot6
+13
Rack 0, Slot 7
Rack 0, Slot 8
+14
Rack 0, Slot 9
Rack 1, Slots 0 to 9
+15 to
19
Rack 2, Slots 0 to 9
+20 to
24
Rack 3, Slots 0 to 9
+25 to
29
Rack 4, Slots 0 to 9
+30 to
34
Rack 5, Slots 0 to 9
+35 to
39
Rack 6, Slots 0 to 9
+40 to
44
Rack 7, Slots 0 to 9
+45 to
49
298
Programming
Settings
Word
Bit(s)
0 to 7
00: 8 ms
10: 0 ms
8 to 15
11: 0.5 ms
0 to 7
12: 1 ms
13: 2 ms
8 to 15
14: 4 ms
0 to 7
15: 8 ms
8 to 15
16: 16 ms
17: 32 ms
0 to 7
Default:
8 to 15
00 (8 ms)
0 to 7
8 to 15
See
Rack 0.
Function
Sets the input response time
(ON response time = OFF
response time) for CJ-series
Basic I/O Units. The default
setting is 8 ms and the setting
range is 0 ms to 32 ms.
This value can be increased to
reduce the effects of chatter-
ing and noise, or it can be
reduced to allow reception of
shorter input pulses.
Section 7-1
Related
When
flags and
setting is
words
read by
CPU Unit
A220 to
At startup.
A259:
Actual
input
response
times for
Basic I/O
Units