Omron CJ - 09-2009 Operation Manual page 351

Programmable controllers
Table of Contents

Advertisement

PLC Setup
Parity
Programming
Console address
Word
Bit(s)
+160
00 to 01
00 Hex: Even
01 Hex: Odd
10 Hex: None
Default: 00
Baud Rate
Programming
Console address
Word
Bit(s)
+161
00 to 07
00 Hex: 9,600 bps
01 Hex: 300 bps
02 Hex: 600 bps
03 Hex: 1,200 bps
04 Hex: 2,400 bps
05 Hex: 4,800 bps
06 Hex: 9,600 bps
07 Hex: 19,200 bps
08 Hex: 38,400 bps
09 Hex: 57,600 bps
0A Hex: 115,200 bps
Default: 00 Hex
Send Delay
Programming
Console address
Word
Bit(s)
+162
00 to 15
0000 to 270F Hex (0
to 99,990 ms)
Unit: 10 ms
Default: 0000
Settings
This setting is valid only in no-protocol com-
munications mode. Set the Standard/Cus-
tom setting (word 160, bit 15) to 1 to enable
this setting.
Settings
This setting is valid only in no-protocol com-
munications mode. Set the Standard/Cus-
tom setting (word 160, bit 15) to 1 to enable
this setting.
Settings
When the TXD(236) instruction is executed,
data will be sent from the RS-232C after the
send delay set here has expired.
Function
Function
Function
Section 7-1
Related
When set-
flags and
ting is read
words
by CPU Unit
A61902
At the next
(RS-232C
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61902
At the next
(RS-232C
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61902
At the next
(RS-232C
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
303