Omron CJ - 09-2009 Operation Manual page 46

Programmable controllers
Table of Contents

Advertisement

Conformance to EC Directives
6-3
Conformance to EC Directives
1,2,3...
6-4
Relay Output Noise Reduction Methods
Countermeasures
xlvi
Note Applicable EMC (Electromagnetic Compatibility) standards are as follows:
EMS (Electromagnetic Susceptibility):
EMI (Electromagnetic Interference):
Low Voltage Directive
Always ensure that devices operating at voltages of 50 to 1,000 V AC and 75
to 1,500 V DC meet the required safety standards for the PLC (EN61131-2).
The CJ-series PLCs comply with EC Directives. To ensure that the machine or
device in which the CJ-series PLC is used complies with EC Directives, the
PLC must be installed as follows:
1. The CJ-series PLC must be installed within a control panel.
2. You must use reinforced insulation or double insulation for the DC power
supplies used for the communications power supply and I/O power sup-
plies.
3. CJ-series PLCs complying with EC Directives also conform to the Com-
mon Emission Standard (EN61000-6-4). Radiated emission characteris-
tics (10-m regulations) may vary depending on the configuration of the
control panel used, other devices connected to the control panel, wiring,
and other conditions. You must therefore confirm that the overall machine
or equipment complies with EC Directives.
The CJ-series PLCs conforms to the Common Emission Standards
(EN61000-6-4) of the EMC Directives. However, noise generated by relay out-
put switching may not satisfy these Standards. In such a case, a noise filter
must be connected to the load side or other appropriate countermeasures
must be provided external to the PLC.
Countermeasures taken to satisfy the standards vary depending on the
devices on the load side, wiring, configuration of machines, etc. Following are
examples of countermeasures for reducing the generated noise.
(Refer to EN61000-6-4 for more details.)
Countermeasures are not required if the frequency of load switching for the
whole system with the PLC included is less than 5 times per minute.
Countermeasures are required if the frequency of load switching for the whole
system with the PLC included is more than 5 times per minute.
EN61000-6-2
EN61000-6-4
(Radiated emission: 10-m regulations)