Technical specifications
Accuracy:
Galvanic separation:
Connections:
Operating temperature:
Storage temperature:
Aux. supply:
Measuring input voltage:
Load:
Measuring input current (In): 1A or /5A AC from current transformer
Load:
Frequency:
Analogue input:
Current:
Impedance:
(From the set point is reached till the output is activated or the delay timer is started).
Multi inputs:
(From the set point is reached till the output is activated and the delay timer is started).
Active binary inputs:
Internal voltage:
Impedance:
RPM input:
Passive binary in voltage:
PM075 REV 2 09/08/20
MEC 310 GENSET CONTROLLER

Technical information

Class 2.0 to EN 60688/IEC 688
Between inputs and aux. power supply: 500V DC – 1 min.
2
1.5 mm
multi stranded
-20...70° C (-4...158° F) (UL/cUL Listed: Max. 50° C ambient)
-40...70° C (-40...158° F)
6-36V DC (UL/cUL Listed: 7.5...32.7V DC) continuously
Max. 8W consumption
50...480V AC phase to phase (+20%)
1.5M Ω
Max. 0.3VA per phase
30...70Hz
From active transducer
0(4)...20mA
50 Ω
Wire break:
I <2.5mA = Fault
Response times:
500ms
Resistor inputs, internal 3V supply
Wire break:
R >150 Ω
Response times:
500ms
Dry contact inputs with wire break
3V DC
240 Ω ~ 16mA
2.0...70V
10...10,000Hz
Bi-directional optocoupler 6...36V DC
Page 21
THOMSON TECHNOLOGY