Generator monitoring
3-phase or single phase generator monitoring
•
Voltage/current/frequency/power factor/power/reactive power
o
Generator protection (ANSI)
Over-/undervoltage (27/59)
•
Over-/underfrequency (81)
•
Overcurrent (51)
•
Reverse power (32)
•
Voltage unbalance (60)
•
Phase sequence error (47)
•
M-logic
Simple logic configuration tool
•
Selectable input events
•
Selectable output commands
•
Clear text display
128 x 64 pixel backlight STN
•
Alarm texts editable
•
All texts in multi-language
•
Clear text alarm messages
•
Clear text diagnostics for both hardwired inputs and CANbus messages (J1939)
•
Log book holding 150 log entries
•
Real time clock for time and date
•
The basic MEC 310 generator controller unit can be equipped with an AMF option needed to
provide a real emergency power system controller. Furthermore, CANbus communication for
different engine types is available and CANbus for up to two EAPs is possible at the same time.
Also Modbus RS485 is available as an option.
A full options list is included in the data sheet.
PM075 REV 2 09/08/20
MEC 310 GENSET CONTROLLER
Options
Page 6
THOMSON TECHNOLOGY