MEC 310 GENSET CONTROLLER

Analogue inputs 0(4)-20mA

The 0(4)-20mA setting can only be set in the TPS 300 software.
4-20mA inputs have wire break detection. The wire break detection limit is 2.5mA.
Settings:
Scale top point value (click the '...').
Alarm setpoint: Freely configurable (click the '...').
Scale low point value.
Tick boxes: Select the needed function.
Unit: E.g. Bar, F, C, PSI.
PM075 REV 2 09/08/20
Page 61