Hz/V Monitoring Settings - THOMSON MEC 310#GENSET CONTROLLER Installation And Operation Manual

Genset controller
Hide thumbs Also See for MEC 310#GENSET CONTROLLER:
Table of Contents

Advertisement

6210 Run/stop (cooling down)
No.
Setting
6211
Run/stop (P1)
6212
Run/stop (P1)
6213
Cool. down temp.
6214
Reference
6220 Hz/V OK
No.
Setting
6221
Hz/V OK *
6222
Hz/V OK *
6223
Hz/V OK *
The setting ranges refer to nominal setting (nominal voltage +/- setting %, nominal
frequency +/- setting Hz).
6290 Idle mode
No.
Setting
6291
Idle mode
6292
Idle mode
6293
Idle mode
Idle mode can be controlled via a binary input. If this is selected, the idle mode remains for as long
as the input is ON. If a binary input is not used, the idle mode can be selected to be active for
manual or auto or both running modes.
- Both manual and auto: Select Man./Auto
- Manual only:
- Auto only:
6320 Engine heater on
No.
Setting
6321
External heater on
6330 Engine heater off
No.
Setting
6331
External heater off
In order to make the external heater function work, a relay must be designated
to this function in the output settings.
PM075 REV 2 09/08/20
MEC 310 GENSET CONTROLLER
Cooling down time
Extended STOP
Cool down temp.
Input for temp. ref.

Hz/V monitoring settings

Timer
Voltage
Frequency
Enable
Timer
Active
Select Man.
Select Auto
Set point
Set point
Page 107
Min. setting
Max. setting
0.0 s
999.0 s
1.0 s
99.0 s
0° C
302° C
VDO 3
EIC
Min. setting
Max. setting
1.0 s
99.0 s
1%
70%
1Hz
20Hz
Min. setting
Max. setting
OFF
ON
1.0 s
300.0 s
Man.
Man./aut.
Min. setting
Max. setting
0 C/F
100 C/F
Min. setting
Max. setting
0 C/F
100 C/F
Factory
setting
240.0 s
5.0 s
70° C
VDO 3
Factory
setting
5.0 s
10%
5Hz
Factory
setting
OFF
5.0 s
Aut.
Factory
setting
10 C/F
Factory
setting
20 C/F