Charger alternator connections
This schematic diagram shows the basic way the charger alternator and the MEC 310 can
cooperate.
Only one running feedback is needed, but for optimal safety and function both the RPM (Tacho)
input and the digital running feedback (D+) can be used as in the example below.
MEC 310
Battery
-
+
Charge
Alternator
Rex:
Excitation resistor:
PM075 REV 2 09/08/20
MEC 310 GENSET CONTROLLER

RPM inputs

Starter
(Crank)
9
23
22
Rex
1N4007
B+
D+
Brush
U
V
W
Exciter
Coil (rotor)
Brush
Stator
Excitation
Controller
12V systems: 47 3 W
24V systems: 100 6 W
Page 62
Running
RPM
Feedback
Input
12
18
17
W
THOMSON TECHNOLOGY