MEC 310 GENSET CONTROLLER

Alarm inhibit

In order to select when the alarms are to be active, a configurable inhibit setting for every alarm has
been made. The inhibit functionality is only available via the PC utility software. For every alarm
there is a drop-down window where it is possible to select which signals that have to be present in
order to inhibit the alarm.
In this example, inhibit is set to Not run status.
Here, the alarm will only be active when the
generator has started and running feedback is
present.
PM075 REV 2 09/08/20
Page 39