The scaling of the 0(4)-20mA inputs for correct display reading can only be done via the TPS 300
software.
4-20mA inputs have wire break function. Wire break alarm will be active when
current goes below 2,5mA. It's not possible to disable the wire break function.
4120 0-20 4-20mA 1.1
No.
Setting
4121
0(4)-20mA 1.1
4122
0(4)-20mA 1.1
4123
0(4)-20mA 1.1
4124
0(4)-20mA 1.1
4125
0(4)-20mA 1.1
4126
0(4)-20mA 1.1
4130 0-20 4-20mA 1.2
No.
Setting
4131
0(4)-20mA 1.2
4132
0(4)-20mA 1.2
4133
0(4)-20mA 1.2
4134
0(4)-20mA 1.2
4135
0(4)-20mA 1.2
4136
0(4)-20mA 1.2
4250 0-20 4-20mA 2.1
No.
Setting
4251
0(4)-20mA 2.1
4252
0(4)-20mA 2.1
4253
0(4)-20mA 2.1
4254
0(4)-20mA 2.1
4255
0(4)-20mA 2.1
4256
0(4)-20mA 2.1
4260 0-20 4-20mA 2.2
No.
Setting
4261
0(4)-20mA 2.2
4262
0(4)-20mA 2.2
4263
0(4)-20mA 2.2
4264
0(4)-20mA 2.2
4265
0(4)-20mA 2.2
4266
0(4)-20mA 2.2
PM075 REV 2 09/08/20
MEC 310 GENSET CONTROLLER

Analogue inputs 0(4)-20mA

Min. setting
Set point
4mA
Delay
0.0 s
Output A
R0 (none)
Output B
R0 (none)
Enable
OFF
Fail class
Min. setting
Set point
4mA
Delay
0.0 s
Output A
R0 (none)
Output B
R0 (none)
Enable
OFF
Fail class
Min. setting
Set point
4mA
Delay
0.0 s
Output A
R0 (none)
Output B
R0 (none)
Enable
OFF
Fail class
Min. setting
Set point
4mA
Delay
0.0 s
Output A
R0 (none)
Output B
R0 (none)
Enable
OFF
Fail class
Page 96
Max. setting
Factory
setting
20mA
10mA
100.0 s
5.0 s
R26 (relay 26)
R0 (none)
R26 (relay 26)
R0 (none)
ON
OFF
See description of fail classes
Max. setting
Factory
setting
20mA
10mA
100.0 s
5.0 s
R26 (relay 26)
R0 (none)
R26 (relay 26)
R0 (none)
ON
OFF
See description of fail classes
Max. setting
Factory
setting
20mA
10mA
100.0 s
5.0 s
R26 (relay 26)
R0 (none)
R26 (relay 26)
R0 (none)
ON
OFF
See description of fail classes
Max. setting
Factory
setting
20mA
10mA
100.0 s
5.0 s
R26 (relay 26)
R0 (none)
R26 (relay 26)
R0 (none)
ON
OFF
See description of fail classes
THOMSON TECHNOLOGY